11 PARAMETERS
Parameters can be edited manually according to the procedures shown in Chapter 10 or via WEBSERVER
as explained in Chapter 8.
11.1
DISPLAY PARAMETERS
To perform a configuration / modification of parameters that control the elevator, follow these steps:
The lists related to each function, instead, provide tools for
advanced configuring and commissioning the
inverter
.
In the list,
the parameters are grouped into families
based on the range of intervention and for each
parameter, as well as a numeric identifier, there is a description of the function performed.
The only parameter that the user can edit are which one star
t with “p”.
The parameters
that start with “r” are a display of the current value of the parameter indicated.
DO NOT CHANGE PARAMETERS FOR WHICH YOU DO NOT KNOWN EFFECT: possibility of
unintended consequences and / or serious physical injury to people and to the system.
11.2
INVERTER COMMISSIONING
All activities below described can be performed alternatively with the BOP or by PC
ATTENTION: You must do self-learning inverter before performing any calibration, in order to
adapt its behavior to the installation characteristics.
To run the self-learning inverter correctly, do the following:
1.
Install and set up the system completely (electrical connections, piping, oil filling the tank,...)
2.
make sure you have the weight that can be loaded to reach the maximum working pressure of the
system (Pmax)
3.
Only if you use PC commissioning, Start the WEBSERVER program, connect the PC ONLINE to the
device
4.
Only if you use PC commissioning, login to the parameter list
User
5.
Make sure the oil temperature (see parameter r21695 Drive) is within the range Tmin=20°C and
Tmax=30°C. In case Toil<20°C, run a few cycles of movement up and down to increase the T oil. If
Toil>30°C, let the oil cool with the system is shut down. If you use PC commissioning, the parameter is
inside the parameters family AUTOTUNING,
6.
Run
the self-learning without load
(
by PC,
Use
, family parameters AUTOTUNING)
:
Remove any load from the cab
Set the parameter P21600=1
Perform a normal cycle of ascent and descent of the lift
Set the parameter P21600 = 0
In this way, the new torque values detected at empty conditions, that are visible to the parameters
r21620 and r21621, are copied and saved in the parameters of the inverter use P21590 and P21595.
7.
Run
the self-learning at full load
(
by PC,
User
, family parameters AUTOTUNING)
:
load the cab with weights to reach Pmax
Set the parameter P21601=1
Perform a normal cycle of ascent and descent of the lift
Set the parameter P21601 = 0
In this way, the new torque values measured at full-load conditions, that are visible to the parameters
visible to r21622 and r21623, are copied and saved in the parameters of the inverter use P21591 and
P21596.
ATTENTION: If the Toil is outside of the range Tmin / Tmax values of auto-tuning will not be captured
and torque values may be setup to 0 generating an unsatisfactory behavior of the inverter and therefore of
the lift.
ATTENTION: If you do not set the parameter to 0 at the end of the test, the system will remain under
self-learning conditions and the system does not work properly.
ATTENTION: If during the procedure is missing voltage, the torque values remain set to 0! Repeat the
tuning after restoring power.
ATTENTION: If you calibrate under conditions other than empty / full load, the torque values recorded
may not ensure proper operation of the system under all conditions.
Содержание 6SL3210-1PE21-1AL0
Страница 1: ...Siemens PM240 2_EN_rev00 30082019 docx 0 1 0 INVERTER SIEMENS S120 PM240 2 for HI POWER UNITS ...
Страница 4: ......
Страница 6: ......
Страница 8: ......
Страница 12: ...3 4 Siemens PM240 2_EN_rev00 30082019 docx Figure 3 PM240 2 frame size FSD FSE ...
Страница 22: ......
Страница 24: ......
Страница 28: ......
Страница 34: ......
Страница 39: ...Siemens PM240 2_EN_rev00 30082019 docx 7 5 ...
Страница 40: ......
Страница 48: ......
Страница 50: ......