Fault and Alarm Messages
09.02
7-10
Siemens AG 6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit Operating Instructions
Alarm
No.
Parameter
No.
⎯⎯
Bit No.
Description
Countermeasures
A049
P956
⎯⎯
0
no Slave
In the case of serial I/O (SCB1 with SCI1/2), no
slave is connected and/or the fiber optic conductor
is interrupted or the slaves have no voltage.
P660 SCI AnalogInConf
Check the slave.
Check the cable.
A050
P956
⎯⎯
1
Slave not ok
In the case of serial I/O, the slaves required
according to the parameter settings are not
available (slave number an/or slave type).
Check
P660 SCI AnalogInConf
A051
P956
⎯⎯
2
Peer Bdrate
In a peer-to-peer connection, the baud rate
selected is too high and/pr different
Match the baud rates of the SCB modules connected to
each (
P684 SST/SCB Baudrate)
A052
P956
⎯⎯
3
Peer PrD-L
In a peer-to-peer connection, an excessive process
data length has been set (>5).
Reduce the number of words
P686 SCom/SCB # PrDat
.
A053
P956
⎯⎯
4
Peer Lng f.
In a peer-to-peer connection, the process data
length of the sender and receiver do not agree
Match the word lengths of the sender and receiver
P686 SCom/SCB # PrDat
A065
P957
⎯⎯
0
Auto Restart
The line voltage is outside the tolerance band at
the moment (e.g. power outage). The firing pulses
are therefore inhibited. On power recovery,
however, the WEA option (P366) implements an
auto restart.
Important
An auto restart may constitute a danger for persons and
property. Make sure you really want to have auto restart
(WEA).
If necessary, change
P366 WEA
.
A081..
A096
r958
⎯⎯
0...15
CB Warning 1...16
See user's manual for the CB module
A097..
A112
r959
⎯⎯
0...15
TB Warning 1 16
See user's manual for the TB module
A113..
A128
r960
⎯⎯
0...15
TB Warning 17...32
See user's manual for the TB module