SIEMENS Energy & Automation
10-51
SIMOREG DC Master Base Drive Panel Operating Instructions
PNU
Description
Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
10.25 Oscillation
Function:
Parameters P480 to P483 define the waveshape of a rectangular signal (oscillation setpoint K0203). The value set in P480 determines the
signal level for the time period set in P481 and the value set in P482 the signal level for the time period set in P483.
Oscillation: Selected in P485. The free-running rectangular signal is switched through to the output K0208.
P480
FDS
(G128)
Oscillation setpoint 1
-199.9 to 199.9
[%]
0.1% of maximum
speed
Ind: 4
FS=0,5
Type: I2
P052 = 3
P051 = 40
Online
P481
FDS
(G128)
Oscillation time 1
0.1 to 300.0
[s]
0.1s
Ind: 4
FS=0.1
Type: O2
P052 = 3
P051 = 40
Online
P482
FDS
(G128)
Oscillation setpoint 2
-199.9 to 199.9
[%]
0.1% of maximum
speed
Ind: 4
FS=-0,4
Type: I2
P052 = 3
P051 = 40
Online
P483
FDS
(G128)
Oscillation time 2
0.1 to 300.0
[s]
0.1s
Ind: 4
FS=0.1
Type: O2
P052 = 3
P051 = 40
Online
P484
*
FDS
(G128)
Source for standard setpoint
Selection of connector to be injected as the output value when the
"Oscillation" function is not selected
0 = connector K0000
1 = connector K0001
etc.
All connector
numbers
1
Ind: 4
FS=209
Type: L2
P052 = 3
P051 = 40
Offline
P485
*
BDS
(G128)
Source for oscillation selection
Selection of binector to control activation of the "Oscillation" function
(log. "1" state = oscillation active)
0 = binector B0000
1 = binector B0001
etc.
All binector numbers
1
Ind: 2
FS=0
Type: L2
P052 = 3
P051 = 40
Offline
10.26 Definition of "Motor interface"
(see also Section 8, Sheets G185
a
nd G186
of Operating Instructions 6RX1700-0AD**
)
CAUTION!
The encoders for measurement and monitoring of the brush length, bearing condition, air flow and motor temperature must be
safely isolated from the power circuit.
P490
*
(G185)
Selection of temperature sensor for analog monitoring of motor
temperature
i001: Temperature sensor at terminals 22 / 23:
i002: Temperature sensor at terminals 204 / 205:
Settings:
0 No
temperature
sensor
1 KTY84
2
PTC thermistor with R=600
Ω
1)
3
PTC thermistor with R=1200
Ω
1)
4
PTC thermistor with R=1330
Ω
1)
5
PTC thermistor with R=2660
Ω
1)
1) PTC thermistor according to DIN 44081 / 44082 with specified R at rated
response temperature, 1330
Ω
on Siemens motors (setting 4 must be
selected). When a PTC thermistor is selected as the temperature
sensor, it is not necessary to set parameters P491 and P492 (alarm and
trip temperatures). These two temperatures are predetermined by the
type of PTC thermistor installed. Whether an alarm or fault is output
when the operating point of the PTC thermistor is reached depends on
how the relevant input is parameterized (P493.F or P494.F).
0 to 5
1
Ind: 2
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
P491
FDS
(G185)
Analog monitoring of motor temperature: Alarm temperature
Operative only when P490.x=1.
0 to 200
[°C]
1°C
Ind: 4
FS=0
Type: O2
P052 = 3
P051 = 40
Online
Содержание 6RA70 Series
Страница 9: ...1 4 Siemens Energy Automation SIMOREG DC Master Base Drive Panel Operating Instructions NOTES ...
Страница 23: ...3 12 Siemens Energy Automation SIMOREG DC Master Base Drive Panel Operating Instructions NOTES ...
Страница 25: ...4 2 Siemens Energy Automation SIMOREG DC Master Base Drive Panel Operating Instructions NOTES ...
Страница 31: ...5 6 Siemens Energy Automation SIMOREG DC Master Base Drive Panel Operating Instructions NOTES ...
Страница 45: ...6 14 Siemens Energy Automation SIMOREG DC Master Base Drive Panel Operating Instructions NOTES ...
Страница 60: ...Siemens Energy Automation 7 15 SIMOREG DC Master Base Drive Panel Operating Instructions NOTES ...
Страница 69: ...7 24 Siemens Energy Automation SIMOREG DC Master Base Drive Panel Operating Instructions NOTES ...
Страница 89: ...8 20 Siemens Energy Automation SIMOREG DC Master Base Drive Panel Operating Instructions NOTES ...
Страница 121: ...9 32 Siemens Energy Automation SIMOREG DC Master Base Drive Panel Operating Instructions NOTES ...
Страница 125: ...10 4 SIEMENS Energy Automation SIMOREG DC Master Base Drive Panel Operating Instructions NOTES ...
Страница 215: ...10 94 SIEMENS Energy Automation SIMOREG DC Master Base Drive Panel Operating Instructions NOTES ...