9-12
Siemens Energy & Automation
SIMOREG DC Master Base Drive Panel Operating Instructions
Fault
Description
No.
Cause as a function of fault value
(r047.001, r949.001 or r949.009 with acknowledged error)
Further information (r047.002 to r047.016)
F042 Tachometer
fault
(active in operating states of – –, I, II)
A check is performed every 20ms to ensure that
(K0287)
EMF
Actual
(K0179)
speed
Actual
is > +5%
If the check result is incorrect for 4 times in succession, the fault message is activated.
The following rule applies:
100% actual speed
= maximum speed
100% actual EMF
= ideal average DC voltage at
α
≥
0, i.e. when the thyristor bridge is fully gated
The ideal DC voltage average value at
α
= 0 is
π
2
3
P078.001
∗
∗
The monitoring function is effective only if the EMF > a % of
π
2
3
P078.001
∗
∗
"a" is a percentage that can be set in parameter P357 (default setting 10%).
The monitoring function is effective only if the armature current is > 2% of the converter rated DC current set in r072.002.
Possible fault causes
♦
Open circuit in tachometer or pulse encoder cable.
♦
Tachometer of pulse encoder cable incorrectly connected.
♦
Pulse encoder supply has failed.
♦
Polarity for actual speed value (P743) is incorrectly set.
♦
Armature circuit data (P110 und P111) are incorrectly set (execute current controller optimization run).
♦
Tachometer or pulse encoder defective
♦
Pulse encoder supply voltage is incorrectly set (P140)
♦
The field polarity is not reversed by the external hardware when the field is reversed.
Fault value:
r047 Index 002 to 016:
1
Open circuit in tachometer or pulse encoder cable
i002 Actual speed value (K0179) in case of fault
2
Polarity of tachometer or pulse encoder is incorrect
i003 Actual EMF value (K0287) in case of fault
Содержание 6RA70 Series
Страница 9: ...1 4 Siemens Energy Automation SIMOREG DC Master Base Drive Panel Operating Instructions NOTES ...
Страница 23: ...3 12 Siemens Energy Automation SIMOREG DC Master Base Drive Panel Operating Instructions NOTES ...
Страница 25: ...4 2 Siemens Energy Automation SIMOREG DC Master Base Drive Panel Operating Instructions NOTES ...
Страница 31: ...5 6 Siemens Energy Automation SIMOREG DC Master Base Drive Panel Operating Instructions NOTES ...
Страница 45: ...6 14 Siemens Energy Automation SIMOREG DC Master Base Drive Panel Operating Instructions NOTES ...
Страница 60: ...Siemens Energy Automation 7 15 SIMOREG DC Master Base Drive Panel Operating Instructions NOTES ...
Страница 69: ...7 24 Siemens Energy Automation SIMOREG DC Master Base Drive Panel Operating Instructions NOTES ...
Страница 89: ...8 20 Siemens Energy Automation SIMOREG DC Master Base Drive Panel Operating Instructions NOTES ...
Страница 121: ...9 32 Siemens Energy Automation SIMOREG DC Master Base Drive Panel Operating Instructions NOTES ...
Страница 125: ...10 4 SIEMENS Energy Automation SIMOREG DC Master Base Drive Panel Operating Instructions NOTES ...
Страница 215: ...10 94 SIEMENS Energy Automation SIMOREG DC Master Base Drive Panel Operating Instructions NOTES ...