Siemens 5WG1 201-2DB12 Скачать руководство пользователя страница 4

Gamma 

instabus

 

Technical product information 

June 2014 

Gamma arina touch sensor                       single 
 

 

double 

 

 

quadruple

 

Technical product information 

 

UP 20x, UP 28x/3 and UP 28x/5 

Update: http://www.siemens.com/gamma 

Subject to change without further notice  

Siemens Building Technologies  

2.16.1.13/4 

Aplication program 

 

25 C0 Sensor Switch 910301

 

 

 

Single, double or quadruple touch sensor for 

-

 

switching on / off / toggle 

-

 

bell function (press on, release off) 

-

 

dimming (with one or two buttons) 

-

 

solar protection control (with one or two buttons) 

-

 

send value (8-bit and 16-bit) 

-

 

send variable value (8-Bit) 

-

 

1-bit and 8-bit scene control 

-

 

forced control 

-

 

second transmission object 

 

8 channel scene controller with 8 scenes per channel 

 

1 LED as orientation light 

 

1 LED per touch area for status annunciation 

 

IR receiver-decoder for 16 IR channels 

 

Room temperature measurement 

 
This application program applies to all Gamma  arina 
touch sensors. 
When expanding the number of touch areas or the func-
tionality (e.g. from UP 201/12 to UP 203/34) the prior 
configuration remains and must only be expanded.  
Configuration and operation of all Gamma  arina  touch 
sensors is identical independent of design and the num-
ber of touch areas.  
 

Commissioning 
 

Programming mode 

Press the programing button short (< 2 s) to enable pro-
gramming mode. This is indicated by the programming 
LED. 
 

Factory setting 

When the programing button is pressed very long (> 20 
s) the device is reset to the default factory settings. This 
is indicated by evenly flashing the programming LED. The 
flashing stops after 5 seconds.

 

 

Note: 

When the programming key is pressed longer (

>2 s…<20 

s

) the device starts connection test. This is a special 

mode for Desigo TRA. The device may be blocked for the 
manufacturer specific functions for approx. 10 seconds 
for the programming mode. This is indicated by briefly 
flashing the programming LED. 

 

 

 

 

Installation notes 

 
The device can be used for permanent installation in dry 
interior rooms and for insertion in distribution boards or 
miniature housings. 
 

V

 

WARNING 

 

The device must be mounted and commissioned by an 
authorised electrician. 

 

The device can be mounted in combination with 
switches and sockets in multi mounting frames, but 
the installation should comply with safety standard or 
regulation. 

 

The prevailing safety rules must be heeded. 

 

For planning and construction of electric installations, 
the relevant guidelines, regulations and standards of 
the respective country are to be considered. 

 
 
 

Содержание 5WG1 201-2DB12

Страница 1: ... 203 2DB13 champagne 5WG1 201 2DB33 5WG1 202 2DB33 5WG1 203 2DB33 with status LED orientation LED scene controller and room temperature sensor ivory white 5WG1 203 2DB14 champagne 5WG1 203 2DB34 with status LED orientation LED scene controller and IR receiver decoder ivory white 5WG1 203 2DB15 champagne 5WG1 203 2DB35 F1 F3 F4 F2 E6 F5 Figure 1 Mounting touch sensor arina E6 Labelling field F1 Mou...

Страница 2: ...pair then this touch area pair may be assigned one of the following functions Dual touch area dimming with stop telegram Dual touch area control of solar protection blinds roller shades Send variable percent value Send variable 8 bit value 1 bit scene control scene 1 and 2 recall save 8 bit scene effect control recall save Forced control Depending on the selected main function another function may...

Страница 3: ... a scene the actuators belonging to that scene must be set to the desired light levels and switch ing states When receiving a save telegram for an 8 bit scene via the 8 bit scene object the scene controller interrogates the current values and states of the actuators via the corre sponding objects and saves these values and states as scene settings for the associated scene number Saved scene values...

Страница 4: ...is identical independent of design and the num ber of touch areas Commissioning Programming mode Press the programing button short 2 s to enable pro gramming mode This is indicated by the programming LED Factory setting When the programing button is pressed very long 20 s the device is reset to the default factory settings This is indicated by evenly flashing the programming LED The flashing stops...

Страница 5: ...LED per touch area for status annunciation e g quadruple switch 8 status LED s IR receiver UP 203 15 UP 203 35 Range of IR transmission approx 20 m under these conditions with IR hand held remote S 425 72 directed in optical direct line of sight at 500 Lux diffuse day light at reception location Connections Bus line Bus terminal black red screwless Ø 0 6 Ø 0 8 mm solid Physical specifications Dime...

Страница 6: ...icator E6 Labelling field length 82 0 15mm width 18 35 0 1mm thickness 0 2 mm E7 IR receiver hole UP 203 x5 only Installation and wiring General description The touch sensor is mounted onto the conduit box together with its mounting frame The mounting frame is not included and therefore has to be ordered separately see current catalog Mounting Mount the mounting frame F1 onto conduit box G1 via mo...

Страница 7: ...unting of the frame F1 Mounting frame F2 Mounting screws G1 Conduit box 86 mm X 86 mm G2 Mounting slots Insert KNX connector H2 Wiring the KNX connector H2 Insert the KNX connector H2 to the touch sensor Please be noted the polarity of bus connection with mark on housing Figure 5 Connect KNX connector F3 Back housing F4 Front housing H1 Pin H2 KNX connector H3 KNX line Installation of main module ...

Страница 8: ...4 Front housing I1 Hole for screwdriver Figure 8 Remove the KNX connector F1 Mounting frame F3 Back housing F4 Front housing H2 KNX connector Remove the back housing F3 Insert screwdriver to the holes J1 and press as showed in Figure 9 Move the back housing out of the mounting frame F1 Pull the KNX connector H2 out from the back housing Figure 9 Remove the back housing F1 Mounting frame F3 Back ho...

Страница 9: ... in mm General notes The operating instructions must be handed over to the client Any faulty device is to be sent together with a return delivery note of the local Siemens office If you have further questions concerning the product please contact our technical support 86 10 4006306090 support ap i bt siemens com Note This product supports two different operation modes KNX and PL Link This document...

Отзывы: