Gamma
instabus
Technical product information
June 2014
Gamma arina touch sensor single
double
quadruple
UP 20x, UP 28x/3 and UP 28x/5
Technical product information
Siemens Building Technologies
Subject to change without further notice
Update: http://www.siemens.com/gamma
2.16.1.13/3
o
off
o
flash, slowly (0,3 Hz)
o
flash, moderately (1 Hz)
o
flash, fast (5 Hz)
The brightness of the orientation light is configurable
and may be controlled via object (e.g. for night opera-
tion).
Additional functions of devices with status LED
Status LED
[Not available with UP 201/12, UP 201/32, UP 202/12,
UP202/32, UP 203/12, 203/32]
The same configuration options as described for the
orientation LED are available for the status LED of a
device.
The brightness of the status LED can be configured
mutually for all status LED and can be influenced via
object (e.g. for night operation).
To find a touch sensor when its associated status LED is
turned off and it is dark, this LED may be configured to
cyclically flash briefly.
Scene controller
[Applies only to UP 203/14, UP 203/34, UP 203/15, UP
203/35]
The scene controller enables integration of those
actuators, which themselves do not provide 8-bit scene
control, into 8-bit scene control schemes. Up to eight
scene channels (A...H) can be controlled. For each
channel one of these functions may be selected:
•
Switching
•
Solar protection control
•
Forced control
•
8-bit value
•
16-bit value
Each channel may be assigned to up to eight different
scene numbers (1...64).
Scenes are recalled with a short touch area press and
saved with a long touch area press.
Before saving a scene the actuators belonging to that
scene must be set to the desired light levels and switch-
ing states.
When receiving a save telegram for an 8-bit scene via the
8-bit scene object the scene controller interrogates the
current values and states of the actuators via the corre-
sponding objects and saves these values and states as
scene settings for the associated scene number.
Saved scene values are only deleted by a new configura-
tion of the device if the parameter “Delete scene memory
after bus voltage recovery” is set to “Yes”.
IR receiver
[Applies only to UP 205/15, UP 205/35]
The device offers a 16 channel IR receiver-decoder.
As described for the single touch areas / touch area pairs
above, each of the 16 IR channels may be either
configured for functions associated with single buttons
or a button pair. Likewise, dependent on the selected
main functions additional functions may be selected. The
16 channel IR hand-held remote S425/72 allows to fully
exploit these possibilities.
The application program already has been loaded in the
factory.
With the ETS (Engineering Tool Software) the specific pa-
rameters and addresses are assigned appropriately, and
downloaded into the device.
Function ex factory:
All touch area pairs are pre-configured for the building
site function for switching (upper touch areas on, lower
touch areas off).
Room temperature measurement
[Applies only to UP 203/14, UP 203/34]
The room temperature can be sent cyclically or on
change of value. For adaptation to local circumstances
the measured room temperature can be adjusted by a
configurable offset value.
•
Temperature measurement range: (0...40°C)
•
Accuracy of the sensor temperature:
±
1.0 K under reference conditions, (15…35 °C);
±
2.0 K under ambient conditions and in measuring
range;
•
Resolution: 0.35K