Siemens 5WG1 201-2DB12 Скачать руководство пользователя страница 2

Gamma 

instabus

 

Technical product information 

June 2014 

Gamma arina touch sensor                       single 
 

 

double 

 

 

quadruple

 

Technical product information 

 

UP 20x, UP 28x/3 and UP 28x/5 

Update: http://www.siemens.com/gamma 

Subject to change without further notice  

Siemens Building Technologies  

2.16.1.13/2 

Common functions 

 

Touch areas 
Depending on the model a touch sensor provides two to 
eight touch areas (Figure 2: A1, A2, B1, B2, C1, C2, D1, 
D2), which vertically function as a touch area pair (A to 
D). 
 

A1

A2

   

B1

A1

B2

A2

   

A2 B2 C2 D2

A1 B1 C1 D1

 

 

Figure 2: Touch areas 

 
Vertically aligned touch areas may be used as a pair of 
touch areas  (e.g. for defined switching  /  dimming, or 
control of shutters and blinds, i.e. with the upper touch 
area  light is turned on and with the lower touch  area 
light is turned off), or as single touch  areas for sending 
values, single-touch-area  switching / dimming or single-
touch-area control of blinds. 
 
Each individual touch area  (A1, A2, B1, B2, C1, C2, D1, 
D2) may be assigned one of the following functions: 

 

Switching (on, off, toggle) 

 

Door bell function  

 

Single touch area dimming 

 

Single  touch area  control of solar protection (blinds, 
roller shades) 

 

1-bit scene control (scene 1 or 2: recall / save) 

 

8-bit scene / effect control (recall, recall / save) 

 

Send value (8-bit value, percent) 

 

Send value (16-bit value, temperature value, brightness 
value) 

 

Forced control 

Depending on the selected main function another 
function may be executed either additionally after a time 
delay (time delay configurable from 100 ms to 655 s) or 
alternatively when the touch area is pressed for a longer 
period.  
When  touch  areas  are configured as a pair then this 
touch area  pair may be assigned one of the following 
functions:  

 

Dual-touch-area dimming with stop telegram 

 

Dual-touch-area  control of solar protection (blinds, 
roller shades) 

 

Send variable percent value 

 

Send variable 8-bit value 

 

1-bit scene control (scene 1 and 2: recall / save) 

 

8-bit scene / effect control (recall / save) 

 

Forced control 

Depending on the selected main function another 
function may be executed additionally after a time delay 
(time delay configurable from 100 ms to 655 s). 
 
These options are available as additional or alternative 
functions for single touch areas or touch area pairs: 

 

Switching (on) 

 

Switching (off) 

 

Send percent value 

 

Send 8-bit value (0…255) 

 

Send temperature value 

 

Send brightness value 

 

Send 16-bit value (0…65535) 

 

1-bit scene control (scene 1: recall / save) 

 

1-bit scene control (scene 2: recall / save) 

 

8-bit scene / effect control: recall 

 

Forced on 

 

Forced off 

 

Deactivate forced control 

 
Acoustic touch response 
The touch sensor has an internal beeper. This is used as a 
response when a touch area is pressed. 
 
Orientation lighting 
The orientation light (LED) of the device may be turned 
on or off continuously or depending on a status object. 
These configuration options are available for the 
orientation light (LED):  

 

LED permanently off 

 

LED permanently on 

 

LED indicates IR activity (only for touch sensor  with IR 
receiver) 

 

LED indicates user operation 

 

LED indicates long touch area press 

 

A binary status object controls the LED for each status 
value on (=1) or off (=0) respectively to either  

o

 

on 

o

 

off 

o

 

flash, slowly (0,3 Hz) 

o

 

flash, moderately (1 Hz) 

o

 

flash, fast (5 Hz) 

 

An analog status object (8-bit value [0...255], percent 
value, 16-bit value [0...65535], temperature value 
[0°C...40°C], brightness value [0...2000 lux] controls 
the LED for each of up to three value ranges 
respectively to either  

o

 

on 

Содержание 5WG1 201-2DB12

Страница 1: ... 203 2DB13 champagne 5WG1 201 2DB33 5WG1 202 2DB33 5WG1 203 2DB33 with status LED orientation LED scene controller and room temperature sensor ivory white 5WG1 203 2DB14 champagne 5WG1 203 2DB34 with status LED orientation LED scene controller and IR receiver decoder ivory white 5WG1 203 2DB15 champagne 5WG1 203 2DB35 F1 F3 F4 F2 E6 F5 Figure 1 Mounting touch sensor arina E6 Labelling field F1 Mou...

Страница 2: ...pair then this touch area pair may be assigned one of the following functions Dual touch area dimming with stop telegram Dual touch area control of solar protection blinds roller shades Send variable percent value Send variable 8 bit value 1 bit scene control scene 1 and 2 recall save 8 bit scene effect control recall save Forced control Depending on the selected main function another function may...

Страница 3: ... a scene the actuators belonging to that scene must be set to the desired light levels and switch ing states When receiving a save telegram for an 8 bit scene via the 8 bit scene object the scene controller interrogates the current values and states of the actuators via the corre sponding objects and saves these values and states as scene settings for the associated scene number Saved scene values...

Страница 4: ...is identical independent of design and the num ber of touch areas Commissioning Programming mode Press the programing button short 2 s to enable pro gramming mode This is indicated by the programming LED Factory setting When the programing button is pressed very long 20 s the device is reset to the default factory settings This is indicated by evenly flashing the programming LED The flashing stops...

Страница 5: ...LED per touch area for status annunciation e g quadruple switch 8 status LED s IR receiver UP 203 15 UP 203 35 Range of IR transmission approx 20 m under these conditions with IR hand held remote S 425 72 directed in optical direct line of sight at 500 Lux diffuse day light at reception location Connections Bus line Bus terminal black red screwless Ø 0 6 Ø 0 8 mm solid Physical specifications Dime...

Страница 6: ...icator E6 Labelling field length 82 0 15mm width 18 35 0 1mm thickness 0 2 mm E7 IR receiver hole UP 203 x5 only Installation and wiring General description The touch sensor is mounted onto the conduit box together with its mounting frame The mounting frame is not included and therefore has to be ordered separately see current catalog Mounting Mount the mounting frame F1 onto conduit box G1 via mo...

Страница 7: ...unting of the frame F1 Mounting frame F2 Mounting screws G1 Conduit box 86 mm X 86 mm G2 Mounting slots Insert KNX connector H2 Wiring the KNX connector H2 Insert the KNX connector H2 to the touch sensor Please be noted the polarity of bus connection with mark on housing Figure 5 Connect KNX connector F3 Back housing F4 Front housing H1 Pin H2 KNX connector H3 KNX line Installation of main module ...

Страница 8: ...4 Front housing I1 Hole for screwdriver Figure 8 Remove the KNX connector F1 Mounting frame F3 Back housing F4 Front housing H2 KNX connector Remove the back housing F3 Insert screwdriver to the holes J1 and press as showed in Figure 9 Move the back housing out of the mounting frame F1 Pull the KNX connector H2 out from the back housing Figure 9 Remove the back housing F1 Mounting frame F3 Back ho...

Страница 9: ... in mm General notes The operating instructions must be handed over to the client Any faulty device is to be sent together with a return delivery note of the local Siemens office If you have further questions concerning the product please contact our technical support 86 10 4006306090 support ap i bt siemens com Note This product supports two different operation modes KNX and PL Link This document...

Отзывы: