3UG4614-.....
Voltage type of control feed voltage
AC
Control supply voltage
•
at 50 Hz at AC rated value
V
160 … 690
•
at 60 Hz at AC rated value
V
160 … 690
Operating range factor control supply voltage rated
value
•
at 50 Hz for AC
1
•
at 60 Hz for AC
1
Impulse voltage resistance rated value
kV
6
Recorded real power
W
2
Protection class IP
IP20
Electromagnetic compatibility
IEC 60947-1 / IEC 61000-6-2 / IEC 61000-6-4
Operating current at 17 V minimum
mA 5
Continuous current of the DIAZED fuse link of the
output relay
A
4
Resistance against vibration according to IEC
60068-2-6
1 ... 6 Hz: 15 mm, 6 ... 500 Hz: 2g
Shock resistance according to IEC 60068-2-27
sinusoidal half-wave 15g / 11 ms
Current carrying capacity of output relay
•
at AC-15
–
at 250 V at 50/60 Hz
A
3
–
at 400 V at 50/60 Hz
A
3
•
at DC-13
–
at 24 V
A
1
–
at 125 V
A
0.2
–
at 250 V
A
0.1
Installation altitude at a height over sea level
maximum
m
2 000
Conductor-bound parasitic coupling BURST
according to IEC 61000-4-4
2 kV
Conductor-bound parasitic coupling conductor-earth
SURGE according to IEC 61000-4-5
2 kV
Conductor-bound parasitic coupling conductor-
conductor SURGE according to IEC 61000-4-5
1 kV
Electrostatic discharge according to IEC 61000-4-2
6 kV contact discharge / 8 kV air discharge
Field-bound parasitic coupling according to IEC
61000-4-3
10 V/m
Thermal current of the contact-affected switching
element maximum
A
5
Insulation voltage for overvoltage category III
according to IEC 60664 with degree of pollution 3
rated value
V
690