3UG458. insulation monitoring relay
9.4 3UG4582/3UG4583 insulation monitoring relays
3UG4 / 3RR2 monitoring relays
Manual, 05/2016, NEB927043002000/RS-AC/004
269
9.4.7.2
3UG4583
Measuring circuit
3UG4583-1CW30
Type of voltage for monitoring
AC/DC
Measurable line frequency
Hz
15 … 400
Network leakage resistance
µF
20
Adjustable response value impedance
•
1
kΩ
1 … 100
•
2
kΩ
2 … 200
General technical details
3UG4583-1CW30
Product function
insulation monitor
•
isolation control
Yes
•
defect storage
Yes
Type of voltage of the controlled supply voltage
AC/DC
Operating frequency
•
rated value
Hz
15 … 400
Control supply voltage
•
for DC
–
rated value
V
24 … 240
•
at 50 Hz at AC
–
rated value
V
24 … 240
•
at 60 Hz at AC
–
rated value
V
24 … 240
Working range factor supply voltage rated value
•
for DC
0.85 … 1.1
•
at 50 Hz
–
for AC
0.85 … 1.1
•
at 60 Hz
–
for AC
0.85 … 1.1
Impulse voltage resistance rated value
kV
4
Thermal current of the contact-affected switching element maximum
A
4
Protection class IP
IP20
Ambient temperature
•
during operating
°C
-25 … +60
Item designation
•
according to DIN EN 61346-2
K
•
according to DIN 40719 extendable after IEC 204-2 according to
IEC 750
K