3UG4641 cos phi and active current monitoring relay
11.7 Technical data
3UG4 / 3RR2 monitoring relays
304
Manual, 05/2016, NEB927043002000/RS-AC/004
3UG4641-.....
Current carrying capacity of output relay
•
at AC-15
–
at 250 V at 50/60 Hz
A
3
–
at 400 V at 50/60 Hz
A
3
•
at DC-13
–
at 24 V
A
1
–
at 125 V
A
0.2
–
at 250 V
A
0.1
Conductor-bound parasitic coupling BURST
according to IEC 61000-4-4
2 kV
Conductor-bound parasitic coupling conductor-earth
SURGE according to IEC 61000-4-5
2 kV
Conductor-bound parasitic coupling conductor-
conductor SURGE according to IEC 61000-4-5
1 kV
Electrostatic discharge according to IEC 61000-4-2
6 kV contact discharge / 8 kV air discharge
Field-bound parasitic coupling according to
IEC 61000-4-3
10 V/m
Thermal current of the contact-affected switching
element maximum
A
5
Insulation voltage for overvoltage category III
according to IEC 60664 with degree of pollution 3
rated value
V
690
Degree of pollution
3
Ambient temperature
•
during operating
°C
-25 … +60
•
during storage
°C
-40 … +85
•
during transport
°C
-40 … +85
Galvanic isolation
•
between entrance and outlet
Yes
•
between the outputs
Yes
•
between the voltage supply and other circuits
Yes
Mechanical operating cycles as operating time
typical
10 000 000
Electrical operating cycles as operating time at
AC-15 at 230 V typical
100 000
Operating cycles with 3RT2 contactor maximum
1/h
5 000