3UG4.1 line monitoring relay
6.7 3UG4617 / 3UG4618 line monitoring relays
3UG4 / 3RR2 monitoring relays
168
Manual, 05/2016, NEB927043002000/RS-AC/004
3UG4617-.....
3UG4618-.....
Starting time after the control supply voltage has
been applied
s
1
Response time maximum
s
0.45
Relative adjustment accuracy
%
0.2
Relative metering precision
%
5
Precision of digital display
+/-1 digit
Relative repeat accuracy
%
1
Type of voltage of the controlled supply voltage
AC
Control supply voltage
•
at 50 Hz at AC rated value
V
160 … 690
•
at 60 Hz at AC rated value
V
160 … 690
Working range factor supply voltage rated value
•
at 50 Hz for AC
1
•
at 60 Hz for AC
1
Impulse voltage resistance rated value
kV
6
Recorded real power
W
2
Protection class IP
IP20
Electromagnetic compatibility
IEC 60947-1 / IEC 61000-6-2 / IEC 61000-6-4
Operating current at 17 V minimum
mA 5
Continuous current of the DIAZED fuse link of
the output relay
A
4
Resistance against vibration according to
IEC 60068-2-6
1 … 6 Hz: 15 mm, 6 … 500 Hz: 2g
Resistance against shock according to
IEC 60068-2-27
sinusoidal half-wave 15g / 11 ms
Current carrying capacity of output relay
•
at AC-15
–
at 250 V at 50/60 Hz
A
3
–
at 400 V at 50/60 Hz
A
3
•
at DC-13
–
at 24 V
A
1
–
at 125 V
A
0.2
–
at 250 V
A
0.1