Trip-free function for the type SDV7-SE
outdoor distribution circuit breaker
For the type SDV7-SE outdoor distribution
circuit breaker, the trip-free function is
accomplished by blocking the movement of
the close latch pawl (62.5.2) when the
manual trip pushbutton is actuated. The trip-
free function is in accord with ANSI/IEEE
C37.04-1999, clause 6.9.a.
Opening (refer to Figure 6: Stored-energy
operating mechanism (circuit breaker shown
in OPEN position) on page 12)
If the circuit breaker is to be opened
manually, the opening spring (64.0) is
released by pressing the OPEN pushbutton
(54.0). In the case of an electrical command
being given, the trip coil 52T (54.1) unlatches
the opening spring (64.0).
The opening spring (64.0) turns the jack shaft
(63.0) via lever (63.5); the sequence being
similar to that for closing.
Rapid auto-reclosing
Since the closing spring is automatically
recharged by the motor operating mechanism
when the circuit breaker has closed, the
operating mechanism is capable of an “Open-
Close-Open” duty cycle as required for rapid
auto-reclosing.
The circuit breaker is suitable for use in
applications with a rated reclosing-time
interval of 0.3 seconds, per ANSI/IEEE C37.06-
2009.
Manual operation
Electrically operated vacuum circuit breakers
can be operated manually if the control
supply should fail.
Manually charging the closing spring
(Refer to Figure 9: Use of manual spring-
operation crank and Figure 10: Manual
spring-charging crank on page 17)
Insert the hand crank (50.0) with the over
running coupling pushed forward (50.6)
through the opening (50.1) onto hand crank
coupling (50.5) and turn it clockwise (about
48 revolutions) until the closing-spring
indicator (55.0) shows CHARGED. The hand
crank is coupled with the charging
mechanism via an over-running coupling;
thus the operator is not exposed to any risk
should the control supply be restored during
manual charging.
Manual closing (refer to Figure 6: Stored-
energy operating mechanism (circuit breaker
shown in OPEN position) on page 12)
Press the close button (53.0). The CLOSE/
OPEN indicator (58.0) will then display
CLOSED and the closing spring condition
indicator (55.0) will now read DISCHARGED.
Manual opening (refer to Figure 6: Stored-
energy operating mechanism (circuit breaker
shown in OPEN position) on page 12)
The opening spring (64.0) is charged during
closing. To open the circuit breaker, press the
Open pushbutton (54.0) and OPEN will be
displayed by indicator (58.0).
The schematic shown in Figure 11: Typical
elementary diagram on page 18 is intended
to aid in understanding the mechanism
operation discussed in this instruction
manual. Refer to the schematic diagram
furnished with your circuit breaker for specific
information.