![Siemens 3AH35-SE Series Скачать руководство пользователя страница 41](http://html.mh-extra.com/html/siemens/3ah35-se-series/3ah35-se-series_instruction-manual_375494041.webp)
41
Technical data and
troubleshooting
Rated
maximum
voltage
Interrupting
class
Rated short-circuit
current
Vacuum
interrupter
Continuous
current
Stroke
2
kV
kA
kA
Type
A
mm
15.5
20
20 [email protected] kV
VSS-17006
1,200, 2,000
7-9
15.5
20
20 [email protected] kV
VS-25008
1,200, 2,000
13-15
15.5
25
25 [email protected] kV
VSS-17006
1,200, 2,000
7-9
15.5
25
25 [email protected] kV
VS-25008
1,200, 2,000
13-15
15.5
31.5
31.5 [email protected] kV
VS-15052
1,200, 2,000, 3,000
7-9
15.5
40
40 [email protected] kV
VS-15052
1,200, 2,000, 3,000
7-9
27.6
20
20 [email protected] kV
VS-25008
1,200, 2,000
13-15
27.6
25
25 [email protected] kV
VS-25008
1,200, 2,000
13-15
38.0
20
20 [email protected] kV
VS-30030
1,200, 2,000, 2,500
18-22
38.0
25
25 [email protected] kV
VS-30030
1,200, 2,000, 2,500
18-22
38.0
31.5
31.5 [email protected] kV
VS-30041
1,200, 2,000, 2,500
18-22
38.0
40
40 [email protected] kV
VS-30041
1,200, 2,000, 2,500
18-22
Table 7: Vacuum interrupter stroke
Footnotes:
1.
The vacuum interrupter type designation is labeled on the vacuum interrupter. If the vacuum interrupter
installed does not match that indicated in this table, contact the nearest Siemens representative.
2.
If you need assistance achieving the indicated stroke setting, contact the nearest Siemens representative.
Содержание 3AH35-SE Series
Страница 46: ...46 Table 13 Remarks ...
Страница 47: ...47 Table 13 Remarks continued ...