background image

PISA-B-8CL2-B1
PISA-B-8CL2-B4

Apr. 2021 / Rev. 0.1 DS-PISA-B-8CL2-Bx-xx-EN

www.pulspower.com

1 / 19

All parameters are specified at 24Vdc input voltage, 8x3.75A output currents, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.

ELECTRONIC FUSE
8X 24V, NEC CLASS 2

Eight Current Controlled Outputs

NEC Class 2 Compliant

Adaptive Voltage-dependent Current Limitation for
Maximal Output Power According to NEC Class 2

Selective Tripping of Overloaded Channels

Compatible even with large Capacitive Loads

Output Currents Displayed Live on LED Matrix

Remote Reset or Reset via Pushbuttons

Common Signaling Relay Contact for Tripped
Channels (PISA-B-8CL2-B1)

Digital Coded Signal Output for Tripped Channels
(PISA-B-8CL2-B4)

Parameter Settings can be Locked by PIN-Code

ON/OFF Feature for Each Individual Output

Easy Wiring - Distribution Terminals for Negative Pole

3 Year Warranty

GENERAL DESCRIPTION

SHORT-FORM DATA

The  PISA-B  devices  are  DIN  rail  mountable
eight  channel  protection  modules  with  integrated
electronic  fuses  for  24V  systems.  They  distribute  the
current  from  one  large  power  source  to  eight  NEC
Class  2  output  circuits,  which  results  in  reduced  fire
safety efforts and easier regulatory testing as well as
approval processes for the end equipment.
Channel  1  and  2  are  optimized  for  loads  with  large
input  capacitances.  Connect  such  loads  to  these
channels to avoid false tripping or unexpected switch-
off such loads.
The  PISA-B-8CL2-B1  is  equipped  with  a  common
tripping  signaling  relay  contact  that  reports  tripped
channels, while the PISA-B-8CL2-B4 has a digital coded
signal output built in for this function.
All  PISA-B  devices  are  equipped  with  push-in
terminals, which are optimized for automated wiring.
The  mechanically  robust  housing  is  made  of  a  high-
grade,  reinforced  molded  material  on  the  front  and
of  an  aluminum  body,  which  permits  surrounding
temperatures up to +70°C.

Input voltage

DC 24V

-20%/+25%

Required input voltage
for turning-on of outputs

19.6Vdc

Input current

40A

Internal consumption

40mA

PISA-B-8CL2-B1

35mA

PISA-B-8CL2-B4

Nominal output current

3.75A

Per channel

Current limitation

5.7A

CH1 and CH2

50A

CH3 to CH8

Tripping characteristics

Slow or Fast

Selectable

Tripping delay
CH1-CH2

2ms – 1.1s

At short circuit

CH3-CH8

<10ms

At short circuit

CH1-CH8

1.1s

For slow tripping at 1.5x
nominal current

CH1-CH8

0.22s

For fast tripping at 1.5x
nominal current

Max load capacitance capability
CH1-CH2

100mF

Per channel

CH3-CH8

20mF

Per channel

Voltage drop per channel
CH1-CH2

45mV

For 3.75A load

CH3-CH8

60mV

For 3.75A load

Standby losses

1W

Power losses

7W

At 8x 3.75A load

Temperature range

-25°C to 70°C

Size (w x h x d)

52x124x130mm

Without DIN rail

Weight

370g / 0.82lb

ORDER NUMBERS

MAIN APPROVALS

Description:

Electronic Fuse PISA-B-8CL2-Bx-xx

Order Number:
PISA-B-8CL2-B1 
Common signaling relay contact
PISA-B-8CL2-B4 Digital coded signal output

Accessories:
BUS-BAR1-L102
: A set for 2 modules
BUS-BAR1-L155: A set for 3 modules
BUS-BAR1-L500: Single piece L=500mm

For details and a complete approval list, see chapter 20.

UL 2367

UL 61010-2-201

IEC 61010

IEC 62368 planned

Содержание DIMENSION PISA-B-8CL2-B1

Страница 1: ...1 is equipped with a common tripping signaling relay contact that reports tripped channels while the PISA B 8CL2 B4 has a digital coded signal output built in for this function All PISA B devices are...

Страница 2: ...anging the information in this data sheet is subject to revision We therefore kindly ask you to always use the latest issue of this document available under www pulspower com No part of this document...

Страница 3: ...acts of the devices Use an appropriately sized 24V power supply which can deliver the peak current required to trip the load channels If peak currents are too low the supply voltage for the protection...

Страница 4: ...he power bus bar of 32A is not exceeded Fuse modules can be lined up on the DIN rail without spacing The power bus bars can be plugged in from the front and must have a length that all plug contacts o...

Страница 5: ...tive and capacitive loads The maximum size of capacitive loads is specified in the table below see Tab 5 1 Larger load capacitors might result in an unintended turn off of the channel More detailed in...

Страница 6: ...typ 120mV For CH1 or CH2 when all channels are loaded with 3 75A typ 60mV For CH3 to CH8 at 3 75A load when all other channels are not loaded typ 135mV For CH3 to CH8 when all channels are loaded with...

Страница 7: ...ry setting is Fast Tripping delay typ 1 1s For all channels in Slow mode at 1 5x nominal current typ 0 22s For all channels in Fast mode at 1 5x nominal current typ 2ms 1 1s For CH1 and CH2 in short c...

Страница 8: ...n for channel 3 at the same time The selected option is shown on the LED matrix for 2 seconds Letter F indicates the fast and the letter S the slow tripping characteristic If only the SET button is pr...

Страница 9: ...with 40 60 of the nominal current Channel 7 is loaded with 0 10 of the nominal current Channel 8 has tripped due to over current 8 Digital Coded Interface PISA B 8CL2 B4 The device is equipped with a...

Страница 10: ...voltage see chapter 19 10 Reset Input A restart of switched off channels can be done either by a button on the unit or by a control signal on the reset input pins 11 12 Therefore push the correspondi...

Страница 11: ...pulspower com 11 19 All parameters are specified at 24Vdc input voltage 8x3 75A output currents 25 C ambient and after a 5 minutes run in time unless otherwise noted 12 Functional Diagram Fig 12 1 Fu...

Страница 12: ...for positive input power bus bar E2 Interconnection for negative return input power bus bar F Set button required for controlling the unit G Channel control buttons Fig 13 1 Front side H LED matrix d...

Страница 13: ...8A and 40 C t b d At 24V 8x3 75A and 25 C t b d At 24V 8x1 88A and 25 C 16 MTBF MTBF stands for Mean Time Between Failure which is calculated according to statistical device failures and indicates rel...

Страница 14: ...iterion A Output lines 2kV Criterion A Surge voltage on input lines EN 61000 4 5 500V Criterion B housing 1kV Criterion B Surge voltage on output lines EN 61000 4 5 500V Criterion B housing 1kV Criter...

Страница 15: ...Humidity 5 to 95 r h According to IEC 60068 2 30 Atmospheric pressure 110 54kPa See Fig 18 2 for details Altitude Up to 5000m 16 400ft See Fig 18 2 for details Over voltage category N A Impulse withs...

Страница 16: ...max 500Vac Power port to signal port max 500Vac Power port signal port to housing Class of protection III A PE Protective Earth connection is not required Degree of protection IP20 According to EN IE...

Страница 17: ...control and laboratory use Particular requirements for control equipment Applicable for US and Canada E File E198865 UL 2367 UL Certificate Recognized component for category QVRQ UL 2367 Standard for...

Страница 18: ...130mm 5 12 The DIN rail height must be added to the unit depth to calculate the total required installation depth Weight 370g 0 82lb DIN rail Use 35mm DIN rails according to EN 60715 or EN 50022 with...

Страница 19: ...upply of the 24V is then only done by one fuse module preferably in the middle because the current is then better distributed in both directions and the permissible current of the power bus bars of 32...

Отзывы: