35
Elementary diagram
An elementary diagram of the primary
circuit is provided on the front panel
of each ground and test device. This
diagram provides a quick reference to the
arrangement of the device and should be
studied prior to each use to confirm that
the device chosen conforms to the
user’s requirements.
Figure 14: Elementary diagram for
device arranged to ground lower
studs type E
Lower stud
test port
Ground
Grounding
switch
Lower stud
(conductive)
Verify connections of upper studs and
lower studs in the switchgear circuit
breaker compartment. Device type E is
designed to ground lower studs, and
device type F is designed to ground upper
studs. Confirm that the device selected
will ground the desired studs in the
switchgear compartment.
Figure 15: Elementary diagram for
device arranged to ground upper
studs type F
Ground
Grounding
switch
Upper stud
(conductive)
Upper stud
test port