19
Electrical operation is performed using a
remote CLOSE-OPEN pushbutton station at
the end of a long cable. The remote CLOSE-
OPEN pushbutton station cable should be
extended to its full length off to the side of
the cell before grounding operations are
attempted. All observers should stand near
the pushbutton operator, and not in front of
the cell being grounded.
Hazardous voltage and high currents.
Can cause death, serious injury and property damage.
Extend the control cable to its full length.
Use the CLOSE-OPEN pushbutton control station as far from the switch-
gear compartment to be grounded as possible and off to the side rather
than in the front.
Make sure that no person is in the area in front of the switchgear
compartment to be grounded.
Hazardous voltage and high currents.
Can cause death, serious injury and property damage.
Read and understand this instruction manual before
each use
of this
ground and test device.
Operate ground and test device outside switchgear unit and confirm
desired operation before inserting ground and test device into
switchgear unit.
Restrict use to qualified persons.