background image

9 / 18

Siemens

Room temperature controller radio set REV24RF../SET

CE1N2206en

Building Technologies

2018-11-07

During startup, REV..DC synchronizes automatically to the time signal (DCF77) from
Frankfurt, Germany. Synchronization takes max. 10 minutes. Synchronization restarts
each time you press the button or move the program selection slider from the RUN
position during these 10 minutes. Siemens recommends to set the desired settings upon
startup, install the REV..DC in the desired location, and not carry out any actions on the
REV..DC for the next 10 minutes.
In normal operation, the REV..DC synchronizes to the radio clock every day at 3:10 a.m.
The time signal from Frankfurt is modulated to a radio signal. The reception of this radio
signal depends on the distance to Frankfurt, atmospheric conditions as well as the
location where the REV..DC is installed. Siemens cannot guarantee that the REV..DC
can receive the time signal from Frankfurt at any time and any place.
The radio clock symbol is deactivated and an error message is displayed if the clock was not
able to synchronize the time for 7 consecutive days. The controller then runs on the internal
quartz.

After you change one or several DIP switch positions, you must press the DIP switch
reset button to reset the DIP switch.
Otherwise, the previous setting remains active!

Access to the expert level

Set the program selection slider to RUN. Press

 and

 simultaneously for 3 seconds, release the buttons, and

within 3 seconds press and hold down

 and

 simultaneously for 3 seconds, release

, and press

 for another 3

seconds. This releases the engineering settings.

 is displayed.

The display first shows language selection with Code 00. Press the buttons

 or

 to navigate the settings.

Confirm settings by pressing

.

Press the operating mode selector

 to exit the engineering settings.

Code list

This entry has no effect if the radio clock either is inactive or not available.
The time signal received from Frankfurt is shifted by the value set in Code 30 (time zone)
if the radio clock is active.
The time is always changed over at 2 a.m. on the Sunday preceding the set date if there
is no radio clock or if it is inactive. The time change is shifted by the value set in Code 30
(time zone) when the radio clock is active.
The time is always changed over at 3 a.m. on the Sunday preceding the set date if there
is no radio clock or if it is inactive.

   Note
   on synchronization

   Note
   on reception

   No reception

J

 DIP switch reset

ON

1

3

4

2

22

11

Z3

2

5

6

7

8

9

Function block

Code

Name

Factory setting

Your setting

Basic settings

00

Language

English

01

Sensor calibration

off

02

Switching differential 2-point

0.5 °C

LCD
optimization

10

Illumination time

10 seconds

11

Background brightness

0

12

Contrast

0

Clock settings

30

Time zone
Deviation from time signal in Frankfurt
(Central European Time CET) (see Note 1)

0 hours

31

Start of daylight saving time (see Note 2)

March 31 (03-31)

32

End of daylight saving time (see Note 3)

October 31 (10-31)

Note 1:

Note 2:

Note 3:

Содержание 24RFDC/SET

Страница 1: ...ooling phases Continuous comfort mode Continuous energy saving mode Protection against frost or overheating Exception day 24 hour operation with max 3 heating or cooling phases A separate temperature setpoint can be entered in automatic mode and for the exception day for each heating or cooling phase Heating zone control Possibility to control cooling equipment Advantage for retrofitting renovatin...

Страница 2: ...on to radio time signal from Frankfurt Germany REV24RFDC Manual override of the receiving relay Type summary Radio set comprising Room temperature controller REV24RF with 7 day time switch Base and receiver RCR10 868 REV24RF SET Radio set comprising Room temperature controller REV24RFDC with 7 day time switch Receiver for time signal from Frankfurt Germany DCF77 Base and receiver RCR10 868 REV24RF...

Страница 3: ...splay Change battery Time of day Alarm Room temperature measured Heating mode Clear text display line max 18 spaces Cooling mode 0 4 8 12 16 20 24 24 hour timeframe with switching pattern with flashing time cursor Weekday max 3 spaces Info Info Weekday block Weekend block Weekday Without language selection Setpoint for comfort mode Setpoint for absence h Time unit Room temperature Absence holiday ...

Страница 4: ...plays queued error messages followed by important information e g time switch programs etc 4 Plus button Increase values set time or make a selection 5 Override button party mode In the time switch program this button allows you to quickly change from the active temperature level to the next and back Thus you can quickly change to energy saving temperature when you leave the apartment for a short ...

Страница 5: ...ode and exception day time switch programs Start of absence Temperature setpoint during absence End of absence RUN Slider position RUN allows for closing the cover Operating modes The controller offers the two time switch programs and Enter a start time and end time for each comfort phase Also comfort temperature setpoint can be freely entered for each comfort phase Between the comfort phases the ...

Страница 6: ...o adapt the switching times and room temperatures only once for each block Switching pattern Blocks You can also enter individual days You can enter the beginning temperature and end of your holidays At the beginning of the holidays the controller switches to the desired holiday temperature and returns to the previously set operating mode at the end of the holidays In holiday mode symbol is displa...

Страница 7: ...layed The currently measured temperature flashes Press or to recalibrate by max 5 C Set DIP switch to OFF and press the DIP switch reset button to save the settings The minimum setpoint limitation of 16 C prevents undesired heat transfer to neighboring spaces in buildings featuring several heating zones DIP switch ON Setpoint limitation 16 35 C DIP switch OFF Setpoint limitation 3 35 C factory set...

Страница 8: ...nd heat output boiler capacity flow temperature DIP switches 7 ON and 8 ON 1 h C For slow controlled systems DIP switches 7 ON and 8 OFF h C For fast controlled systems DIP switches 7 OFF and 8 ON h C For medium controlled systems DIP switches 7 OFF and 8 OFF OFF Off no effect factory setting Press the DIP switch reset button to save the settings Key for diagram T Temperature C t Forward shift of ...

Страница 9: ...N Press and simultaneously for 3 seconds release the buttons and within 3 seconds press and hold down and simultaneously for 3 seconds release and press for another 3 seconds This releases the engineering settings is displayed The display first shows language selection with Code 00 Press the buttons or to navigate the settings Confirm settings by pressing Press the operating mode selector to exit ...

Страница 10: ...ttings remain unchanged The clock starts at 12 p m the date on 01 01 08 01 January 2008 During the reset all display fields are lit and can be checked accordingly All user defined settings plus expert settings Press the DIP switch reset button ON 1 3 4 2 2211Z32 5 6 7 8 9 and simultaneously for 5 seconds After the reset all factor settings are reloaded This applies to the program selection slider ...

Страница 11: ... room temperature measured Mount the unit base for the REV24RF in the desired location See also Mounting and commissioning notes Attach the base first and then slide the unit in the base from top to bottom You can mount the base on most commercially available recessed conduit boxes or directly on the wall When mounting on a wall make sure there is sufficient clearance above the unit to allow for r...

Страница 12: ...tabs on the battery contact Select desired language by or Confirm by If possible mount the receiver temporarily e g using dual sided adhesive tape to try to identify the best possible location for RF reception To do this fully wire the RCR10 868 and close the front cover See Point 4 Test radio link identify best RF reception location a Switch on RCR10 868 b Press the Test button on the rear or the...

Страница 13: ... Learn button for about 4 seconds The blue LED_2 flashes slowly learning mode is active b Also press the Learn button within 20 minutes on the REV24RF The REV24RF now either shows confirmation that receiver RCR 01 RCR02 etc is connected or that connection failed Display on the RCR10 868 When connection is successful the blue LED_2 briefly flashes quickly and LED_1 goes from red to green If connect...

Страница 14: ...from by flying parts Do not allow the batteries to come into contact with water Do not charge the batteries Do not damage or destroy the batteries Do not heat the batteries to more than 85 C WARNING Electrolyte leakage Chemical burns Only grasp damaged batteries using suitable protective gloves If electrolyte comes into contact with eyes immediately rinse eyes with plenty of water Consult a doctor...

Страница 15: ...ed on EU regulation 813 2013 Eco design directive and 811 2013 Labelling directive concerning space heaters combination heaters the following classes apply Application with On Off operation of a heater PMW TPI room thermostat for use with On Off output heaters Class I value 1 Class IV value 2 Degree of protection IP20 Operation Climatic conditions Temperature Humidity 3K3 as per IEC 60721 3 3 5 40...

Страница 16: ...r h Storage and transport Climatic conditions Temperature Humidity Mechanical conditions Class 2K3 as per IEC 60721 3 2 25 70 C 93 r h Class 2M2 as per IEC 60721 3 2 Without packaging RCR10 868 REV24RF SET 0 16 kg 0 45 kg Housing front Housing bottom RAL 9003 signal white RAL 7038 gray Housing with base 88 x 114 x 31 5 mm The documents can be downloaded from http siemens com bt download Connection...

Страница 17: ... E1 N2 Zone valve Cooling unit Y1 2252S04 M1 N2 T N1 Circulating pump with precontrol by manual mixing valve E1 Cooling unit F1 Thermal reset limit thermostat F2 Manual reset safety limit thermostat M1 Circulating pump N1 Room temperature controller transmitter REV24RF N2 Receiver RCR10 868 N3 Room temperature controller transmitter REV24RF N4 Receiver RCR10 868 Y1 3 port valve with manual adjustm...

Страница 18: ...nd Ltd Building Technologies Division International Headquarters Theilerstrasse 1a CH 6300 Zug Tel 41 58 724 2424 Siemens Switzerland Ltd 2008 2018 Technical specifications and availability subject to change without notice www siemens com buildingtechnologies Dimensions Room temperature controller transmitter REV24RF Receiver RCR10 868 ...

Отзывы: