Room temperature controller radio set REV24RF../SET

CE1N2206en

Building Technologies

2018-11-07

You can freely adjust the setpoints for the weekly and 24-hour operating modes.
Setting range for all setpoints without setpoint limitation 3…35 °C.
Setting range for all setpoints with setpoint limitation 16…35 °C.

Factory setting for heating

Factory setting for cooling

,

,

,

20 °C

24 °C

,

16 °C

28 °C

8 °C

35 °C

12 °C

30 °C

Factory settings: Switching times

Comfort phases

P1

P2

P3

P4

P5

P6

1.

07:00

23:00

PASS

PASS

PASS

PASS

2.

06:00

08:00

17:00

22:00

PASS

PASS

3.

06:00

08:00

11:00

13:00

17:00

22:00

Three different switching patterns are available to simplify entry of switching times. These
can be assigned as blocks to the corresponding weekdays 1…5 and weekend days
6…7. As a result, you need to adapt the switching times and room temperatures only
once for each block.

Switching pattern

Blocks

You can also enter individual days

 …

.

You can enter the beginning, temperature and end of your holidays. At the beginning of
the holidays, the controller switches to the desired holiday temperature and returns to the
previously set operating mode at the end of the holidays.
In holiday mode, symbol

 is displayed along with the end of holiday mode.

Proceed as follows to enter your settings:

Set slider to position 15 (start of absence):  Press

 or

 to set the start date

for your holidays.

Set slider to position 16 (temperature during absence):  Press

 or

 to set

the desired temperature while on holidays.

Set slider to position 17 (end of absence):  Press

 or

 to set the end date

for your holidays.

RUN

Return the slider to position RUN. Symbol

 is displayed to the left of the

symbol.
Press

,

,

,

 or move the slider to end holiday mode prematurely.

Setpoints

Factory setting

7-day time switch

Enter holidays or
absences

Содержание 24RFDC/SET

Страница 1: ...ooling phases Continuous comfort mode Continuous energy saving mode Protection against frost or overheating Exception day 24 hour operation with max 3 heating or cooling phases A separate temperature setpoint can be entered in automatic mode and for the exception day for each heating or cooling phase Heating zone control Possibility to control cooling equipment Advantage for retrofitting renovatin...

Страница 2: ...on to radio time signal from Frankfurt Germany REV24RFDC Manual override of the receiving relay Type summary Radio set comprising Room temperature controller REV24RF with 7 day time switch Base and receiver RCR10 868 REV24RF SET Radio set comprising Room temperature controller REV24RFDC with 7 day time switch Receiver for time signal from Frankfurt Germany DCF77 Base and receiver RCR10 868 REV24RF...

Страница 3: ...splay Change battery Time of day Alarm Room temperature measured Heating mode Clear text display line max 18 spaces Cooling mode 0 4 8 12 16 20 24 24 hour timeframe with switching pattern with flashing time cursor Weekday max 3 spaces Info Info Weekday block Weekend block Weekday Without language selection Setpoint for comfort mode Setpoint for absence h Time unit Room temperature Absence holiday ...

Страница 4: ...plays queued error messages followed by important information e g time switch programs etc 4 Plus button Increase values set time or make a selection 5 Override button party mode In the time switch program this button allows you to quickly change from the active temperature level to the next and back Thus you can quickly change to energy saving temperature when you leave the apartment for a short ...

Страница 5: ...ode and exception day time switch programs Start of absence Temperature setpoint during absence End of absence RUN Slider position RUN allows for closing the cover Operating modes The controller offers the two time switch programs and Enter a start time and end time for each comfort phase Also comfort temperature setpoint can be freely entered for each comfort phase Between the comfort phases the ...

Страница 6: ...o adapt the switching times and room temperatures only once for each block Switching pattern Blocks You can also enter individual days You can enter the beginning temperature and end of your holidays At the beginning of the holidays the controller switches to the desired holiday temperature and returns to the previously set operating mode at the end of the holidays In holiday mode symbol is displa...

Страница 7: ...layed The currently measured temperature flashes Press or to recalibrate by max 5 C Set DIP switch to OFF and press the DIP switch reset button to save the settings The minimum setpoint limitation of 16 C prevents undesired heat transfer to neighboring spaces in buildings featuring several heating zones DIP switch ON Setpoint limitation 16 35 C DIP switch OFF Setpoint limitation 3 35 C factory set...

Страница 8: ...nd heat output boiler capacity flow temperature DIP switches 7 ON and 8 ON 1 h C For slow controlled systems DIP switches 7 ON and 8 OFF h C For fast controlled systems DIP switches 7 OFF and 8 ON h C For medium controlled systems DIP switches 7 OFF and 8 OFF OFF Off no effect factory setting Press the DIP switch reset button to save the settings Key for diagram T Temperature C t Forward shift of ...

Страница 9: ...N Press and simultaneously for 3 seconds release the buttons and within 3 seconds press and hold down and simultaneously for 3 seconds release and press for another 3 seconds This releases the engineering settings is displayed The display first shows language selection with Code 00 Press the buttons or to navigate the settings Confirm settings by pressing Press the operating mode selector to exit ...

Страница 10: ...ttings remain unchanged The clock starts at 12 p m the date on 01 01 08 01 January 2008 During the reset all display fields are lit and can be checked accordingly All user defined settings plus expert settings Press the DIP switch reset button ON 1 3 4 2 2211Z32 5 6 7 8 9 and simultaneously for 5 seconds After the reset all factor settings are reloaded This applies to the program selection slider ...

Страница 11: ... room temperature measured Mount the unit base for the REV24RF in the desired location See also Mounting and commissioning notes Attach the base first and then slide the unit in the base from top to bottom You can mount the base on most commercially available recessed conduit boxes or directly on the wall When mounting on a wall make sure there is sufficient clearance above the unit to allow for r...

Страница 12: ...tabs on the battery contact Select desired language by or Confirm by If possible mount the receiver temporarily e g using dual sided adhesive tape to try to identify the best possible location for RF reception To do this fully wire the RCR10 868 and close the front cover See Point 4 Test radio link identify best RF reception location a Switch on RCR10 868 b Press the Test button on the rear or the...

Страница 13: ... Learn button for about 4 seconds The blue LED_2 flashes slowly learning mode is active b Also press the Learn button within 20 minutes on the REV24RF The REV24RF now either shows confirmation that receiver RCR 01 RCR02 etc is connected or that connection failed Display on the RCR10 868 When connection is successful the blue LED_2 briefly flashes quickly and LED_1 goes from red to green If connect...

Страница 14: ...from by flying parts Do not allow the batteries to come into contact with water Do not charge the batteries Do not damage or destroy the batteries Do not heat the batteries to more than 85 C WARNING Electrolyte leakage Chemical burns Only grasp damaged batteries using suitable protective gloves If electrolyte comes into contact with eyes immediately rinse eyes with plenty of water Consult a doctor...

Страница 15: ...ed on EU regulation 813 2013 Eco design directive and 811 2013 Labelling directive concerning space heaters combination heaters the following classes apply Application with On Off operation of a heater PMW TPI room thermostat for use with On Off output heaters Class I value 1 Class IV value 2 Degree of protection IP20 Operation Climatic conditions Temperature Humidity 3K3 as per IEC 60721 3 3 5 40...

Страница 16: ...r h Storage and transport Climatic conditions Temperature Humidity Mechanical conditions Class 2K3 as per IEC 60721 3 2 25 70 C 93 r h Class 2M2 as per IEC 60721 3 2 Without packaging RCR10 868 REV24RF SET 0 16 kg 0 45 kg Housing front Housing bottom RAL 9003 signal white RAL 7038 gray Housing with base 88 x 114 x 31 5 mm The documents can be downloaded from http siemens com bt download Connection...

Страница 17: ... E1 N2 Zone valve Cooling unit Y1 2252S04 M1 N2 T N1 Circulating pump with precontrol by manual mixing valve E1 Cooling unit F1 Thermal reset limit thermostat F2 Manual reset safety limit thermostat M1 Circulating pump N1 Room temperature controller transmitter REV24RF N2 Receiver RCR10 868 N3 Room temperature controller transmitter REV24RF N4 Receiver RCR10 868 Y1 3 port valve with manual adjustm...

Страница 18: ...nd Ltd Building Technologies Division International Headquarters Theilerstrasse 1a CH 6300 Zug Tel 41 58 724 2424 Siemens Switzerland Ltd 2008 2018 Technical specifications and availability subject to change without notice www siemens com buildingtechnologies Dimensions Room temperature controller transmitter REV24RF Receiver RCR10 868 ...

Отзывы: