For complex controlled systems, simple two-position controller with
0.5 °C switching difference (factory setting).
Press the DIP switch reset button to save the settings.
Only applicable with controlled circulating pump or valve!
This function protects the pump or valve during extended OFF periods against possible
seizure caused by liming. Periodic pump run is activated every 24 hours at 12 p.m. for
three minutes (symbol is displayed during active pump run).
DIP switch ON: Pump run ON.
DIP switch OFF: Pump run OFF (factory setting).
Press the DIP switch reset button to save the settings.
Optimization advances the switch-on point P.1 to ensure that the selected setpoint is
reached at the desired time. The setting depends on the controlled system, i.e., on heat
transmission (piping system, radiators), building dynamics (building mass, insulation),
and heat output (boiler capacity, flow temperature).
DIP switches 7 ON and 8 ON:
1 h/°C For slow controlled systems.
DIP switches 7 ON and 8 OFF: ¼ h/°C For fast controlled systems.
DIP switches 7 OFF and 8 ON: ½ h/°C For medium controlled systems.
DIP switches 7 OFF and 8 OFF: OFF
Off, no effect (factory setting).
Press the DIP switch reset button to save the settings.
Key for diagram:
T
Temperature (°C)
t
Forward shift of switch-on point (h)
TRx
Room temperature actual value
Pon
Starting point for optimized heat-up time.
The controller can be switched over for cooling applications on DIP switch 9.
DIP switch 9 ON:
Cooling
DIP switch 9 OFF:
Heating (factory setting).
Press the DIP switch reset button to save the settings.
Only applicable to REV..DC (with integrated DCF77 receiver to receive time signal from
Frankfurt, Germany)!
DIP switch ON: Clock run by controller-internal quartz.
DIP switch OFF:
Time signal DCF77 from Frankfurt, Germany.
Press the DIP switch reset button to save the settings.
E
Periodic pump run
and anti-lime function:
DIP switch 6
F
Start optimization:
DIP switches 7 and 8
G
Operating mode heating
or cooling:
DIP switch 9
H
Radio clock:
DIP switch 10