Electrical Connections
2.2 Power connection
Table 2-1
Description of the diagram
No.
Description
No.
Description
1
M5 connecting studs
5
M10 grounding studs
2
M10 connecting studs
6
M4 connecting studs
3
M4 grounding stud
BR
Brake connection
4
M6 grounding stud
Table 2-2
Connections for the terminal box
Terminal box
type
Cable gland
Max. outer
cable
diameter
3)
[mm]
Max.
current
[A]
1)
Power
connection
Max.
cross-section
per phase
Ground
connection
Brake
connection
2)
gk130
1 x Pg29
30
36
3 x M4
1 x 6 mm
2
M4
1.5 mm
2
gk230
1 x Pg29
30
66
3 x M5
1 x 16 mm
2
M4
1.5 mm
2
gk420
1 x Pg36
37
104
4 x M10
1 x 35 mm
2
M6
1.5 mm
2
gk630
2 x M32 x 1.5
25
112
3 x M10
2 x 16 mm
2
M10
–––
gk630
2 x M40 x 1.5
32
176
3 x M10
2 x 35 mm
2
M10
–––
gk630
2 x M50 x 1.5
41
209
3 x M10
2 x 50 mm
2
M10
–––
1)
Data acc. to DIN EN 60204-1 (routing type C, ambient temperature 40° C)
2)
BR/BR2 (terminal strip, only for versions with brake)
3)
Dependent on the seal used
1FT6 synchronous motors
2-4
Configuration Manual, (PFT6), Edition 12.2004, 6SN1197-0AD12-0BP0
Содержание 1FT6031-4AK71-4AH0-Z
Страница 3: ... VLQDPLFV RQILJXUDWLRQ 0DQXDO GLWLRQ 6 QFKURQRXV 6HUYRPRWRUV 7 ...
Страница 4: ......
Страница 8: ......
Страница 14: ...Foreword 1FT6 synchronous motors viii Configuration Manual PFT6 Edition 12 2004 6SN1197 0AD12 0BP0 ...
Страница 20: ...Table of Contents 1FT6 synchronous motors xiv Configuration Manual PFT6 Edition 12 2004 6SN1197 0AD12 0BP0 ...
Страница 266: ......
Страница 267: ......