background image

Safety Precautions

(a) Only qualified persons familiar
with the construction and operation
of this equipment should perform
work described in this set of 
instructions. Such work should be
performed only after reading this
complete set of instructions.

(b) Follow safety related work 
practices, as described in NFPA 70E,
part II, at all times.

(c) Hazardous voltages in electrical
equipment can cause severe personal
injury or death. Energizing this
equipment for the first time after 
initial installation or maintenance is
potentially dangerous. Inspection
and maintenance should be 
performed on this equipment and
equipment to which power has been
cut off, disconnected, and electrically
isolated so that no accidental contact
can be made with energized parts.

(d )Some types of electrical 
equipment will cause harmonics in
the electrical system which may
result in overheating. Consider this
condition when determining this
equipment loading, as possible 
de-rating of equipment may be 
necessary.

Important

The information contained herein is
general in nature and not intended
for specific application purposes. It
does not relieve the user of 
responsibility to use sound practices
in application, installation, operation,
and maintenance of the equipment
purchased. Siemens reserves the
right to make changes in the 
specifications shown herein or to
make improvements at any time
without notice or obligations. Should
a conflict arise between the general

adhere to the following warnings:

(a) 

Danger! 

High Voltage. Qualified

personnel only. Lock off all power to
this equipment before working
inside. Always work on de-energized
equipment. Always de-energize
equipment before performing any
tests, maintenance or repair.

(b) 

Warning!

Always perform 

maintenance on the interrupting
device after the closing
mechanism(s) are discharged.

(c) 

Caution!

Always let an interlock

device or safety mechanism perform
its function without forcing or
defeating the device.

(d)

Caution!

Hydrocarbon spray 

propellants and hydrocarbon 
compounds will cause degradation of
certain plastics. Contact your local
Siemens representative before using
these products to clean or lubricate
components during installation or
maintenance.

information contained in this 
publication and the contents of
drawings or supplementary material
or both, the latter shall take 
precedence.

Qualified Person

For the purpose of this manual and
product labels, a qualified person is
one who is familiar with the 
installation, construction, operation
or maintenance of the equipment
and the hazards involved. In addition,
this person has the following 
qualifications:

(a) 

is trained and authorized

to 

de-energize, clear, ground, and tag
circuits and equipment in accordance
with established safety practices.

(b) 

is trained

in the correct care and

use of protective equipment such as
rubber gloves, hard hat, safety 
glasses or face shields, flash clothing,
etc., in accordance with established
safety practices.

(c) 

is trained

in rendering first aid.

Signal Words

The signal words 

"Danger,"

"Warning" 

and 

"Caution" 

used in this

manual indicate the degree of hazard
that may be encountered by the user.
These words are defined as:

Danger - 

Indicates an imminently

hazardous situation which if not
avoided, will result in death or 
serious injury.

Warning -

Indicates a potentially 

hazardous situation which, if not
avoided, could result in death or 
serious injury.

Caution - 

Indicates a potentially 

hazardous situation which, if not
avoided, may result in minor or 
moderate injury.

Dangerous Procedures

In addition to other procedures
described in this manual as 
dangerous, user personnel must

P1 Panel with i-3 Control Technology

TM

1

Содержание 1-3 Control Technology p1 Series

Страница 1: ...utomation Inc All Rights Reserved Siemens is a registered trademark of Siemens AG Product names mentioned may be trademarks or registered trademarks of their respective companies Specifications are subject to change without notice PBSA I3CON 0207 New 4M0207MW Printed in USA s i 3 Control TechnologyTM Instruction Manual P N 12 A 1094 01 Rev 1 p1 series 12 A 1094 01ManualCover qxd 4 9 2007 9 13 AM P...

Страница 2: ... Always perform maintenance on the interrupting device after the closing mechanism s are discharged c Caution Always let an interlock device or safety mechanism perform its function without forcing or defeating the device d Caution Hydrocarbon spray propellants and hydrocarbon compounds will cause degradation of certain plastics Contact your local Siemens representative before using these products...

Страница 3: ... Inspection and Testing 13 Overview 13 Inspection 13 Testing 13 Energizing 13 System Diagnostic Test 13 Chapter 5 Maintenance 14 Chapter 6 System Components 15 BQD Breaker 15 Description 15 Installing BQD breakers into panel 16 Removing BQD breakers from panel 17 Control POD CPOD 17 Description 17 Installing CPOD into panel 20 Removing CPOD from panel 21 Data Rail 21 Description 21 Installing data...

Страница 4: ...ld particular problems arise which are not covered sufficiently for the purchaser s purposes the matter should referred to the local Siemens sales office The contents of this instruction manual shall not become part of or modify any prior of existing agreement commitment or relationship The sales contract contains the entire obligation of Siemens The warranty contained in the contract between the ...

Страница 5: ...n designed to operate in a system having the short circuit interrupting specified in the job specification If for any reason the equipment is later used in a different system user must receive approval of intended changes from Siemens Siemens Type P1 Lighting Panel with i 3 Control Technology is designed to function efficiently under normal operation conditions It is designed and manufactured in a...

Страница 6: ...e Class 2 wire barrier is intentionally misplaced on the figure above to show the ribbon cable Box Can Data Rail BQD Breaker CPOD Class 2 Wire Barrier Neutral Extension i 3 Controller MLO Main Breaker Space Data Rail No Feed Through Lug Ribbon Cable Class 2 Wire Barrier Ground Bar Neutral Extension Figure 1 2 Panel Overview Diagram 5 ...

Страница 7: ...rier immediately Notify the Siemens Sales Office of any shortages or damages Shipping Damage Claim Procedure Note Improper treatment by consignee of visible shipping damage prior to signing the delivery receipt can determine the outcome of the damage claim to be filed Notification to carrier within the 15 day limit on concealed damage is essential if loss resulting from unsettled claims is to be e...

Страница 8: ...e or its finish Refer to Table 2 1 below for approximate weights of single panel with full control points which will be helpful in determining the required capacity of the handling means Panel Size Estimated Weight 18 Circuit Panel 77 lbs 30 Circuit Panel 98 lbs 42 Circuit Panel 119 lbs Table 2 1 P1 Panel Main Lug with i 3 Control Technology Estimated Weight Storage P1 Series Lighting Panel with i...

Страница 9: ...ive or explosive fumes dust vapors dripping or standing water abnormal vibration shock or tilting or other unusual operating conditions For installation replacement of i 3 Control Technology in Siemens P1 panel the following conditions have to be met 1 Branch circuit breakers are Siemens BQD type breakers up to 20A 2 The panel gutter has to be clear only wires for electrical loads are allowed in t...

Страница 10: ... front may be used with i 3 Control Technology Controller installed Control panels from the factory will have an extended opening to allow access to controller program input area For retrofit desiring this feature contact a Siemens sales representative for ordering information 9 Note For repair or replacement of panel components use existing hardware If existing hardware is damaged or lost contact...

Страница 11: ...ter 3 Installation P1 Interior with i 3 CONTROL TECHNOLOGY Installation P1 Interior with i 3 Control Technology may be factory assembled which means that P1 interior components and i 3 Control Technology components are installed and assembled prior to shipment Figure 3 3 below shows the interior mounting holes location Figure 3 2 below illustrates i 3 Control Technology Components Figure 3 2 i 3 C...

Страница 12: ...d in the panel please refer to the step by step installation instructions described on Chapter 6 System Components Additional BQD Breaker and CPOD Installation In case additional BQD breakers and CPODs need to be installed in the panel please refer to the step by step installation instructions described on Chapter 6 System Components under BQD Breaker and CPOD sections Location for Low Voltage Con...

Страница 13: ...to i 3 I O Controller User Guide P N 12 A 1095 01 for the i 3 I O Controller or i 3 System Controller User Guide P N 12 A 1095 02 for i 3 System Controller Deadfront Installation Prior to completing the installation of panel dead front and trim first examine the Inspection section in Chapter 3 Installation Chapter 4 Inspection and Testing 1 Make sure the dead front is installed prior to closing of...

Страница 14: ...o running dielectric or megger testing on the panel and or system 2 All breakers should be exercised prior to energizing 3 The CPOD may be manually closed to allow circuit testing prior to commissioning of the controller Energizing 1 Panelboard deadfront and trim must be installed before energizing 2 In order to minimize risk of injury or damage there should be no load on the P1 panel when it is e...

Страница 15: ...further information be desired or should particular problems arise which are not covered sufficiently for the purchaser s purposes the matter should be referred to the local Siemens sales office Dangerous voltages are present in the equipment which can cause death serious injury or property damage Always disconnect and lock off all power to the equipment before maintenance Maintenance should be pe...

Страница 16: ...0V AC 40o C Catalog Number Catalog Number 15A BQD115 BQD215 20A BQD120 BQD220 Table 6 1 BQD Catalog Numbers Available in April 2007 Interrupting Ratings RMS Symmetrical Amperes Number KA of Poles Volts AC 120 240 277 480 1 65 14 2 65 14 Table 6 2 BQD Interruption Ratings Figure 6 1 BQD 15A Breaker Side View Figure 6 2 BQD 15A Breaker Top V Load Lug Terminal BQD Line Connection Breaker Handle Load ...

Страница 17: ...e screw first otherwise go to the next step 6 Engage the load side mounting of the BQD breaker into the slot of the top barrier to secure the breaker position as shown in figure 6 3 below 7 Align the BQD line connection hole with the tapped hole on the panel bus bar as shown in figure 6 4 below 8 Install and tighten the screw to the torque requirements found on the panel labeling Chapter 6 System ...

Страница 18: ... the loads will be con nected to the load lug of the CPOD The CPOD has a lug of the same size as the circuit breaker on the opposite side from the tab for installing a load wire The CPOD also contains electronics which will allow it to communicate to an I O controller board in the panel The CPOD connector has a 4 wire connection to the data rail A data rail will provide the means of connecting the...

Страница 19: ...ent that connects the circuit breaker to the CPOD B Mechanical Status Provides the open close status of the CPOD Indicator contacts C Manual Override Allows the customer to override the remote command to close the CPOD contacts D CPOD Load Lug The terminal that connects CPOD to the lighting loads E CPOD Connector 4 pin connector that links CPOD to the data rail Table 6 4 CPOD Components 18 CPOD Ca...

Страница 20: ...ability to override the remote commands to the CPOD The contact on the CPOD can be forced to a closed position by manually rotating the switch in clock wise direction using a flat head screwdriver or similar device as shown in figure 6 7 below To re open contacts system must be commissioned This feature is designed to apply current on the circuit prior to commissioning system D CPOD Load Lug The C...

Страница 21: ...ure 6 8 and 6 9 Ensure that the CPOD tang engages into the terminal of the breaker 7 Tighten the screw of the BQD terminal to the torque requirements found on the circuit breaker labeling to ensure electrical connection is established 8 If the data rail is already installed install the CPOD data wire connector into the respective data rail connector as shown in figure 6 10 CPOD data wire connector...

Страница 22: ...he data rail provides a barrier to isolate the power wiring from the Class 2 signal wiring used to operate the relays Each CPOD connects to data rail via a connector that extends out of the CPOD The connector has 4 wire leads as described in CPOD section On the end of the data rail a 26 wire ribbon connector is used to connect data rail to I O printed circuit board There are 3 available data rail ...

Страница 23: ...n in figure 6 13 5 Install and tighten the screws 4 total on each data rail to secure the data rail position 6 Loosen the screw 2 total that secures the data rail lid as shown in figure 6 14 to open the lid for CPOD and ribbon cable connections 7 Close the lid and tighten the screws to secure the data rail lid once all the connections are properly made Chapter 6 System Components Panel deadfront s...

Страница 24: ...stall the screw 4 total from the data rail mounting bracket and panel deadfront support bracket Neutral Extension Description The neutral extension is an adapter piece that mounts to the neutral of the panel This device allows the user to gain additional low amperage neutral connections when the CPODs partially cover the normal neutrals The neutral extension provides connection for 18 wires rangin...

Страница 25: ...utral extension connection to the sub feed neutral bar Torque requirements are on the back of panel deadfront Removing Neutral Extension From Panel 1 Disconnect and lock off all power sources supplying this panel 2 Remove P1 Panel trim and dead front 3 Remove all neutral wires connected to the neutral extension connection points 4 Loosen and uninstall the screws total 2 on each side from the neutr...

Страница 26: ...ement Fuse Element Figure 6 18 Front View of i 3 Controller For more detailed information about the i 3 Controller configuration and set up procedures please refer to the i 3 Controller User Guide Ribbon Cable Mounting Bracket Wiring Access Switch Inputs and Analog I O 25 i 3 Controller Description Figure 6 18 below shows the front view of i 3 controller ...

Страница 27: ...nal to one of the main bus as shown in figure 6 21 and tighten per torque requirement on the back of panel deadfront 7 Connect red wire to phase terminal installed in step 6 as shown in figure 6 21 8 Connect white wire to neutral terminal as shown in figure 6 21 9 Connect green wire to panelboard ground terminal as shown in figure 6 21 Chapter 6 System Components Figure 6 19 Installing i 3 Control...

Страница 28: ...ons 8 Loosen and uninstall the screws 4 total from the mounting brackets 9 The i 3 controller is ready to be removed Ribbon Cables Description Ribbon cable is a 26 wire connection used to connect the I O Board and a data rail Ribbon cable carries two way communication data from I O Board to CPODs and vice versa including power and ground A pair of ribbon cables is required for each panel one for e...

Страница 29: ...ure which means that the connector can only be installed in one orientation Figures 6 23 and 6 24 show the ribbon cable connection to the I O board Chapter 6 System Components Figure 6 23 i 3 Controller I O Board with cover removed Keying Polarized Feature Figure 6 24 Ribbon Cable Connection to Data Rail Figure 6 25 Data Rail PCB Note Do not force inserting the ribbon cable connector on the opposi...

Страница 30: ... 250A Main Breaker 100A 250A Panel Circuits 18 30 42 Branch Ratings 15 20A Branch Disconnect Device BQD Feed Through Lugs N A Remote Operated Relay Ratings 15 20A Remote Operated Relay Device CPOD Data Rail 9 15 21 circuits each side Power Supply Ratings 120 277V AC Fuse Ratings 2A Class CC Enclosure Heights Inches in 32 38 44 Appendix A P1 with i 3 Control Technology Panel Specification 29 ...

Страница 31: ...Label Location 15 A 1047 01 Deadfront kit label On the inside of the deadfront below the controller s cutout 11 C 1044 01 Data Rail rating label On the top cover of the data rail housing 11 C 1045 01 Controller rating label On the top face of the controller to the right side 11 C 1047 01 Fuse rating label On the side of the fuse housing next to the On Off Switch 30 ...

Страница 32: ...i 3 Control Technology replacement parts list please refer to i 3 P1 deadfront kit label P N 15 A 1047 01 which is located on the inside of the panel deadfront Appendix C i 3 Control Technology Spare Parts 31 ...

Страница 33: ...ice Call us at 1 800 964 4114 or visit www sea siemens com sales salesoffices html Warranty Support and Customer Service Contact local sales office For complete details on i 3 Controller configuration Refer to i 3 I O Controller User Guide P N 12 A 1095 01 i 3 I O Controller or i 3 System Controller User Guide P N 12 A 1095 02 Appendix D Customer Service Support Information 32 ...

Страница 34: ...utomation Inc All Rights Reserved Siemens is a registered trademark of Siemens AG Product names mentioned may be trademarks or registered trademarks of their respective companies Specifications are subject to change without notice PBSA I3CON 0207 New 4M0207MW Printed in USA s i 3 Control TechnologyTM Instruction Manual P N 12 A 1094 01 Rev 1 p1 series 12 A 1094 01ManualCover qxd 4 9 2007 9 13 AM P...

Отзывы: