IV306E e SP133E
Figure 10: Dimensions to install the UPS
Pag. 2 di 6
Figure 10B: Size 80-100kVA 6-pulse and 50- 80kVA 12-pulse
The UPS can be closed at wall; the 200mm dimensions is only for reference.
When it is impossible provide for a sufficient gaps from the wall, a suitable length of cables
must be provided to remove the UPS in case of extraordinary repairs.
The shaded arrows show the air flow (in order to minimise the dust intake, the cooling air
is sucked from top and discharged from bottom side).
1000 min
750min
866
350
700
1415