FORM 7: SYSTEM DATA
e
7a: 20/80kVA
SIZE
20
30
40
50
60
80
1a) AC/AC Efficiency (6-pulse)
- 100% nominal load
%
89,89
90,1
90,41
90,53
90,66
91,52
- 75% nominal load
%
90,5
90,65
90,75
90,88
91,01
91,99
- 50% nominal load
%
90,08
90,12
90,2
90,34
90,49
91,66
- 25% nominal load
%
85,84
85,86
86,01
86,62
87,24
88,57
2a) Maximum Heat dissipation @ Full
Load (6 pulse)
kW
1,8
2,6
3,4
4,2
4,9
5,9
1b) AC/AC Efficiency (12-puse)
- 100% nominal load
%
88,72
88,93
89,23
90,32
90,36
90,37
- 75% nominal load
%
89,32
89,47
89,57
90,20
90,69
91,41
- 50% nominal load
%
88,91
88,95
89,03
89,30
89,84
90,03
- 25% nominal load
%
84,72
84,74
84,89
86,63
87,28
87,93
2b) Maximum Heat dissipation @ Full
Load (12-pulse)
kW
2,0
3,0
3,9
4,3
5,1
6,8
3) Noise @ 1 metre as per ISO3746
dBA
60
60
60
60
60
60
4) Air Flow
m
3
/h
1200
1200
1200
1200
1200
1200
5) Operating Temperature
°C
0 ÷ 40
0 ÷ 40
0 ÷ 40
0 ÷ 40
0 ÷ 40
0 ÷ 40
6) Storage Temperature
°C
-20 / 70
-20 / 70
-20 / 70
-20 / 70
-20 / 70
-20 / 70
7) Maximum relative humidity (non
condensing):
(@ 40°C)
%
60
60
60
60
60
60
(@ 25°C)
%
90
90
90
90
90
90
8) Elevation without derating
m
1000
1000
1000
1000
1000
1000
9) Power derating over 1000m each
1000m
%
0,987 1,013171
e
SIZE
100
120
160
200
1a) AC/AC Efficiency (6pulse)
- 100% nominal load
%
91,63
92,82
92,87
93,01
- 75% nominal load
%
92,34
92,63
93,40
93,31
e
- 50% nominal load
%
91,25
91,25
91,86
93,05
- 25% nominal load
%
89,65
87,28
87,74
89,22
2a) Maximum Heat dissipation @ Full
Load
kW
7,3
7,4
9,8
12,0
1b) AC/AC Efficiency (12pulse)
- 100% nominal load
%
90,44
91,61
91,66
91,80
- 75% nominal load
%
91,14
91,43
92,19
92,10
- 50% nominal load
%
90,06
90,06
90,67
91,84
- 25% nominal load
%
88,48
86,15
86,60
88,06
2b) Maximum Heat dissipation @ Full
Load
kW
8,5
8,8
11,6
14,3
3) Noise @ 1 metre as per ISO3746
dBA
60
60
60
60
4) Air Flow
m
3
/h
1200
2000
3200
3200
5) Operating Temperature
°C
0 ÷ 40
0 ÷ 40
0 ÷ 40
0 ÷ 40
6) Storage Temperature
°C
-20 / 70
-20 / 70
-20 / 70
-20 / 70
7) Maximum relative humidity (non
condensing):
(@ 40°C)
%
60
60
60
60
(@ 25°C)
%
90
90
90
90
8) Elevation without derating
m
1000
1000
1000
1000
9) Power derating over 1000m each
1000m
%
5
7b: 100/200kVA
5
IV306E - SP133E
Siel S.p.A.