5.2.6
Operation in potentially explosive atmospheres
Depending on the respective device version, the FLSE100-XT sender/receiver units are
designed for use in potentially explosive atmospheres:
Table 1
Device versions
Version
Approval
IECEX
ATEX
NEC/CEC (USA/CA)
F1F-S
Ex db [ia Ga] IIA T4 Ga/Gb
Ex db [la Ga] IIB T4 Ga/Gb
Ex db [ia Ga] IIC T6/T4 Ga/Gb
Ex ia IIC T6/T4 Ga
II 1/2G Ex db [ia Ga] IIA T4 Ga/Gb
II 1/2G Ex db [la Ga] IIB T4 Ga/Gb
II 1/2G Ex db [ia Ga] IIC T6/T4 Ga/Gb
II 1G Ex ia IIC T6/T4 Ga
Class I, Division 1, Group D, T4;
Class I, Zone 1, Ex/AEx d[ia] IIA, T4;
Class I, Division 2, Group D, T4;
Class I, Zone 2, Ex/AEx nA[ia] IIA, T4
Class I, Division 1, Groups C and D, T4;
Class I, Zone 1, Ex/AEx d[ia] IIB, T4;
Class I, Division 2, Groups C and D, T4;
Class I, Zone 2, Ex/AEx nA[ia] IIB, T4
Class I, Division 1, Groups B, C and D, T4;
Class I, Zone 1, Ex/AEx d[ia] IIB + H2, T4;
Class I, Division 2, Groups A, B, C and D, T4;
Class I, Zone 2, Ex/AEx nA[ia] IIC, T4
F1F-M
Ex db [ia Ga] IIA T4 Ga/Gb
Ex db [la Ga] IIB T4 Ga/Gb
Ex db [ia Ga] IIC T6/T4 Ga/Gb
Ex ia IIC T6/T4 Ga
II 1/2G Ex db [ia Ga] IIA T4 Ga/Gb
II 1/2G Ex db [la Ga] IIB T4 Ga/Gb
II 1/2G Ex db [ia Ga] IIC T6/T4 Ga/Gb
II 1G Ex ia IIC T6/T4 Ga
Class I, Division 1, Group D, T4;
Class I, Zone 1, Ex/AEx d[ia] IIA, T4;
Class I, Division 2, Group D, T4;
Class I, Zone 2, Ex/AEx nA[ia] IIA, T4
Class I, Division 1, Groups C and D, T4;
Class I, Zone 1, Ex/AEx d[ia] IIB, T4;
Class I, Division 2, Groups C and D, T4;
Class I, Zone 2, Ex/AEx nA[ia] IIB, T4
Class I, Division 1, Groups B, C and D, T4;
Class I, Zone 1, Ex/AEx d[ia] IIB + H2, T4;
Class I, Division 2, Groups A, B, C and D, T4;
Class I, Zone 2, Ex/AEx nA[ia] IIC, T4
F1F-H
Ex db IIC T6/T4 Gb
II 2G Ex db IIC T6/T4 Gb
Class I, Division 1, Groups B, C and D, T4;
Class I, Zone 1, Ex/AEx d IIB + H2, T4;
Class I, Division 2, Groups A, B, C and D, T4;
Class I, Zone 2, Ex/AEx nA IIC, T4
F1F-P
Ex db [ia Ga] IIA T4 Ga/Gb
Ex db [ia Ga] IIB T4 Ga/Gb
Ex db [ia Ga] IIC T6/T4 Ga/Gb
II 1/2G Ex db [ia Ga] IIA T4 Ga/Gb
II 1/2G Ex db [ia Ga] IIB T4 Ga/Gb
II 1/2G Ex db [ia Ga] IIC T6/T4 Ga/Gb
Class I, Division 1, Group D, T4;
Class I, Zone 1, Ex/AEx d[ia] IIA, T4;
Class I, Division 2, Group D, T4;
Class I, Zone 2, Ex/AEx nA[ia] IIA, T4
Class I, Division 1, Groups C and D, T4;
Class I, Zone 1, Ex/AEx d[ia] IIB, T4;
Class I, Division 2, Groups C and D, T4;
Class I, Zone 2, Ex/AEx nA[ia] IIB, T4
Class I, Division 1, Groups B, C and D, T4;
Class I, Zone 1, Ex/AEx d[ia] IIB + H2, T4;
Class I, Division 2, Groups A, B, C and D, T4;
Class I, Zone 2, Ex/AEx nA[ia] IIC, T4
Содержание FLOWSIC100 Flare-XT
Страница 8: ...Contents 8 FLOWSIC100 Flare XT Operating Instructions 8023761 V1 0 2020 10 SICK Engineering GmbH ...
Страница 12: ...12 FLOWSIC100 Flare XT Operating Instructions 8023761 V1 0 2020 10 SICK Engineering GmbH About this document ...
Страница 146: ...146 FLOWSIC100 Flare XT Operating Instructions 8023761 V1 0 2020 10 SICK Engineering GmbH Maintenance ...
Страница 150: ...150 FLOWSIC100 Flare XT Operating Instructions 8023761 V1 0 2020 10 SICK Engineering GmbH Troubleshooting ...
Страница 170: ...170 FLOWSIC100 Flare XT Operating Instructions 8023761 V1 0 2020 10 SICK Engineering GmbH Technical data ...
Страница 187: ...Annex FLOWSIC100 Flare XT Operating Instructions 8023761 V1 0 2020 10 SICK Engineering GmbH 187 ...