Project planning
4.3
Determining the installation location of the Interface Unit
4.3.1
Installation location requirements
▸
Fit the Interface Unit in an easily accessible and protected position.
▸
Providing suitable cables are used, the Interface Unit can be installed up to 1000 meters
from the sender/receiver units. The installation of a flameproof version of the interface unit
directly on site is therefore unnecessary in many situations. For easier access to the
Interface Unit, we recommend installation in a control room (measuring station or similar).
This considerably simplifies communication with the FLOWSIC100 Flare-XT for
configuration or location of failure or error causes.
4.3.2
Clearance for fitting the Interface Unit
NOTICE:
The Interface Unit is only suitable for vertical installation.
NOTICE:
Содержание FLOWSIC100 Flare-XT
Страница 8: ...Contents 8 FLOWSIC100 Flare XT Operating Instructions 8023761 V1 0 2020 10 SICK Engineering GmbH ...
Страница 12: ...12 FLOWSIC100 Flare XT Operating Instructions 8023761 V1 0 2020 10 SICK Engineering GmbH About this document ...
Страница 146: ...146 FLOWSIC100 Flare XT Operating Instructions 8023761 V1 0 2020 10 SICK Engineering GmbH Maintenance ...
Страница 150: ...150 FLOWSIC100 Flare XT Operating Instructions 8023761 V1 0 2020 10 SICK Engineering GmbH Troubleshooting ...
Страница 170: ...170 FLOWSIC100 Flare XT Operating Instructions 8023761 V1 0 2020 10 SICK Engineering GmbH Technical data ...
Страница 187: ...Annex FLOWSIC100 Flare XT Operating Instructions 8023761 V1 0 2020 10 SICK Engineering GmbH 187 ...