Installation Interface Unit
FLOWSIC100 Flare-XT · Operating Instructions · 8023761/V1-0/2020-10 · © SICK Engineering GmbH
119
6.6
Connecting shielding terminals
1
Strip the cable > 22 mm.
2
Leave a piece of the sheath in place to
hold the wires together. As an alternative,
use a cable strap.
3
Before securing the cable with the
terminal, attach the associated plug-in
connector.
Then connect the terminal to the shield.
4
Press the terminal down and slide it onto
the rail to secure the cable.
WARNING:
Danger due to incorrect use of the shielding terminal
The insulation of the cable must not be clamped under the shielding terminal.
Otherwise there is no electrical contact and shielding is not guaranteed.
> 22 mm
Содержание FLOWSIC100 Flare-XT
Страница 8: ...Contents 8 FLOWSIC100 Flare XT Operating Instructions 8023761 V1 0 2020 10 SICK Engineering GmbH ...
Страница 12: ...12 FLOWSIC100 Flare XT Operating Instructions 8023761 V1 0 2020 10 SICK Engineering GmbH About this document ...
Страница 146: ...146 FLOWSIC100 Flare XT Operating Instructions 8023761 V1 0 2020 10 SICK Engineering GmbH Maintenance ...
Страница 150: ...150 FLOWSIC100 Flare XT Operating Instructions 8023761 V1 0 2020 10 SICK Engineering GmbH Troubleshooting ...
Страница 170: ...170 FLOWSIC100 Flare XT Operating Instructions 8023761 V1 0 2020 10 SICK Engineering GmbH Technical data ...
Страница 187: ...Annex FLOWSIC100 Flare XT Operating Instructions 8023761 V1 0 2020 10 SICK Engineering GmbH 187 ...