COMMISSIONING
5.3
Connecting analog devices
5.3.1
Pressure transmitter
1
Go to menu item “Configuration/Run/Pressure”.
2
Set the “Meter pressure input type” to “Analog input”.
Fig. 27: Configuration/Run/Pressure
3
Go to menu item “IO/Diagnostics/Analog inputs”.
“Analog input 1 input value” must be between 4 mA and 20 mA. If this is not the case,
the function of the transmitter must be checked and whether there are any error values
defined by the device.
Adjusting the scale in the flow computer to the working range of the transmitter
1
Go to menu item “IO/Diagnostics/Analog inputs”.
2
Set the value for “Analog input 1 full scale” to the maximum value of the measuring
range of the pressure transmitter.
3
Set the value for “Analog input 1 zero scale” to the minimum value of the measuring
range of the pressure transmitter.
Fig. 28: IO/Diagnostics/Analog inputs