COMMISSIONING
5
5.2
Connecting devices with HART protocol
▸
Connect the transmitters as described in Section “Electrical installation”.
5.2.1
Pressure sensor
1
Go to menu item “Configuration/Run/Pressure”.
2
Set the “Meter pressure input type” to “HART”.
Fig. 24: Configuration/Run/Pressure
3
Go to menu item “IO/Diagnostics/Analog inputs”.
The value of “Analog input 1 input value” must be 4 mA.
Fig. 25: IO/Diagnostics/Analog inputs (pressure sensor)
5.2.2
Temperature transmitter
1
Go to menu item “Configuration/Run/Pressure”.
2
Set the “Meter pressure input type” to “HART”.
3
Go to menu item “IO/Diagnostics/Analog inputs”.
The value of “Analog input 2 input value” must be 4 mA.
Fig. 26:
IO/Diagnostics/Analog inputs (temperature sensor)
Observe the following: Minor deviations are possible (typically <= +/-0.01mA).
Observe the following: Minor deviations are possible (typically <= +/-0.01mA).