Chapter
5
Operating Instructions
CLP 100 Bar Code Reader
Electrical installation
18
©
SICK AG · Division Auto Ident · Germany · All rights reserved
8 008 912/0000/21-08-2002
5.4.4
Wiring the terminal interface
As an alternative the PC may be connected to the terminal interface.
Figure 5-2
shows the wiring of the terminal interface.
Note
The terminal interface is a TTL level interface.
5.4.5
Wiring the "Sensor" switching input
If a reading process is to be triggered via an external sensor, connect the sensor to the
"Sensor" switching input. This triggering type is selected as the default setting of the CLP
100.
Figure 5-3
shows the wiring of the "Sensor" switching input.
Table 5-5
lists the
characteristic data of this switching input.
¾
Connect the sensor as described in
Figure
.
Hint
The D
EVICE
CONFIGURATION
tab card of the CLP Setup software can be used to modify the
response time of the "Sensor" input (debouncing).
*) 9-pin internal D-Sub plug to PC
Fig. 5-2:
Wiring the terminal interface
Fig. 5-3:
Wiring of the "Sensor" switching input
Switching
performance
Connecting GND to the input starts the read port of the CLP 100 (low)
Properties
Not electrically separated
Electrical values
Low
(Read port active):
High
(Read port inactive):
Tab. 5-5: Characteristic data of the "Sensor" switching input
7
3 *
8
2 *
5
5 *
5
GND
"Sensor"
CLP 100
1
Sensor
5 V
0 V
V
S
0.8 V
≤
≤
I
1.5
µ
A
≤
2.4 V
V
S
5 V
≤
≤
I
1.5
µ
A
≤