SHINKO-4/5 ton High Efficiency A5 Duct Technical Manual
35
For multiple unit installations, units must be spaced a minimum of 915mm apart. (Coil face to face.
If the unit is to be installed on a hot sun exposed roof or a black-topped ground area, the unit should
be raised sufficiently above the roof or ground to avoid taking the accumulated layer of hot air into the
outdoor unit. At the same time, an adequated structural support for the unit is necessary.
In case any obstacles exist above the outdoor unit, such obstacles must be 1,524mm above the
outdoor unit.
Ground installation:
✓
The unit may be installed at ground level on a solid base that will not shift or settle, causing strain
on the refrigerant lines and possible leaks.
✓
Install the unit in a level position.
✓
Normal operating sound levels may be objectionable if the unit is placed directly under windows of
certain rooms, such as bedrooms, study rooms.
✓
Top of the unit discharge area must be unrestricted for at least 1,530mm above the unit.
✓
The outdoor unit should not be installed in an area where mud or ice could cause personal injury
or system damage.
✓
Elevate the unit sufficiently to prevent any blockage of the air entrances by snow in areas where
there will be snow accumulation. Check the local weather bureau for the expected snow
accumulation in your area. Isolate the unit from rain gutters to avoid any possible wash out of the
foundation.
Roof installation:
✓
When installing units on a roof, the structure must be capable of supporting the total weight of the
unit, including a padded frame unit, rails, etc., which should be used to minimize the transmission
of sound or vibration into the conditioned space.
Unit placement:
✓
Provide a base in the pre-determined location.
✓
Remove the shipping carton and inspect for possible damage.
✓
Compressor tie-down nuts should remain tightened.
✓
Position the unit on the base provided.
✓
This system uses R410A refrigerant which operates at higher pressure than R22. No other
refrigerant may be used in this system. Gauge sets, hoses, refrigerant containers, and recovery
Содержание SOVC-48CN1-RC7C
Страница 13: ...SHINKO Tropical R410A High Efficient A5 Duct Technical Manual 50Hz 12 6 Wiring Diagrams STB 48CWN1 STB 60CWN1 ...
Страница 22: ...SHINKO 4 5 ton High Efficiency A5 Duct Technical Manual 21 3 Service Space ...
Страница 23: ...SHINKO 4 5 ton High Efficiency A5 Duct Technical Manual 22 4 Wiring Diagrams SOVC 48CN1 RC7C SOVC 60CN1 RC5C ...
Страница 47: ...SHINKO 4 5 ton High Efficiency A5 Duct Technical Manual 46 Power supply phase sequence error ...
Страница 48: ...SHINKO 4 5 ton High Efficiency A5 Duct Technical Manual 47 Lack of Phase A B and C of power supply ...
Страница 50: ...SHINKO 4 5 ton High Efficiency A5 Duct Technical Manual 49 Over current protection of compressor ...
Страница 53: ...SHINKO 4 5 ton High Efficiency A5 Duct Technical Manual 52 Eeprom error ...