SHINKO-4/5 ton High Efficiency A5 Duct Technical Manual
23
5.
Ele
ctric Characteristics
Model
Outdoor Unit
Power Supply
Compressor
OFM
Hz
Voltage
Min.
Max.
MCA
MOP
MFA
LRA RLA
KW
FLA
SOVC-48CN1-RC7C
50
380-415V 198V
254V
13.3
20
20
72
8.6
0.320
1.5
SOVC-60CN1-RC5C
50
380-415V 198V
254V
14.1
25
25
76
10.1
0.320
1.5
Remak:
MCA: Min. Current Amps. (A) MOP: Rating of Overcurrent Protective Devices(A)
MFA: Max. Fuse Amps. (A) LRA: Locked Rotor Amps. (A)
RLA: Rated Locked Amps. (A) OFM: Outdoor Fan Motor.
FLA: Full Load Amps. (A) KW: Rated Motor Output (kW)
6.
Sound Levels
Model
Sound pressure level
SOVC-48CN1-RC7C
62dB(A)
SOVC-60CN1-RC5C
63dB(A)