7.4 Negative Acknowledgement
7.4.1 Error code 1 (31H, Shinko protocol) or Exception code 2 (02H, Modbus protocol)
The slave will return Error code 1 (31H, Shinko protocol) or Exception code 2 (02H, Modbus protocol) in the
following case.
• When non-existent data item is read or written.
7.4.2 Error code 3 (33H, Shinko protocol) or Exception code 3 (03H, Modbus protocol)
The slave will return Error code 3 (33H, Shinko protocol) or Exception code 3 (03H, Modbus protocol) in the
following case.
• When a value out of the setting range is written.
7.4.3 Error code 4 (34H, Shinko protocol) or Exception code 17 (11H, Modbus protocol)
The slave will return Error code 4 (34H, Shinko protocol) or Exception code 17 (11H, Modbus protocol) in the
following cases.
• When 0001H (AT/Auto-reset Perform) or 0002H (AT on startup Perform) is written at 00E6H (AT/Auto-reset
Perform/Cancel) during PI control or ON/OFF control action.
• While AT is performing during Fixed value control, if 0001H (AT/Auto-reset Perform) or 0002H (AT on startup
Perform) is written at 00E6H (AT/Auto-reset Perform/Cancel).
While AT is performing in Fixed value control, and if 00E0H (OUT/OFF key function) is written.
• While AT is performing during Program control, if 0001H (AT/Auto-reset Perform) or 0002H (AT on startup
Perform) is written at 00E6H (AT/Auto-reset Perform/Cancel).
While AT is performing during Program control, and if 00E0H (OUT/OFF key function) is written.
• When 00E5H (Manual control MV) is written during automatic control
7.4.4 Error code 5 (35H, Shinko protocol) or Exception code 18 (12H, Modbus protocol)
The slave will return Error code 5 (35H, Shinko protocol) or Exception code 18 (12H, Modbus protocol) in the
following case.
• During setting mode by keypad operation