7.1.5 A Single/Multiple Piece(s) of Data Read/Write Command (for Program Control)
(20/24/50/54H: 20H/24H/50H/54H, 03/06/10H: 03H/06H/10H)
Shinko
Command
Type
Modbus
Function
Code
Data Item
(*10)
Data
20/24/50/54H
03/06/10H
1000H Step 1 SV
(*11)
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
1001H Step 1 time
(*13)
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
1002H Step 1 wait value
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
1003H Step 2 SV
(*12)
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
1004H Step 2 time
(*13)
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
1005H Step 2 wait value
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
1006H Step 3 SV
(*12)
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
1007H Step 3 time
(*13)
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
1008H Step 3 wait value
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
1009H Step 4 SV
(*12)
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
100AH Step 4 time
(*13)
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
100BH Step 4 wait value
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
100CH Step 5 SV
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
100DH Step 5 time
(*13)
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
100EH Step 5 wait value
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
100FH Step 6 SV
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
1010H Step 6 time
(*13)
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
1011H
Step 6 wait value
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
1012H Step 7 SV
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
1013H Step 7 time
(*13)
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
1014H Step 7 wait value
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
1015H Step 8 SV
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
1016H Step 8 time
(*13)
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
1017H Step 8 wait value
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
1018H Step 9 SV
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
1019H Step 9 time
(*13)
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
101AH Step 9 wait value
Set value, Decimal point ignored
20/24/50/54H
03/06/10H
101BH Reserved
(*2)
:
:
:
:
20/24/50/54H
03/06/10H
102FH Reserved
(*2)
(*1) If any action is changed at 0006H (Event output EV1 allocation) or 0007H (Event output EV2 allocation), EV1 alarm value, EV2 alarm value, etc.
will revert to factory default value.
For the items to be initialized: Refer to Section ‘7.7 Items to be Initialized by Changing Settings’ (p.44).
(*2) For ‘Reserved’ items, if a single/multiple piece(s) of data Read is/are executed, acknowledgement will be returned (but data is 0).
If a single/multiple piece(s) of data is/are written, data will be discarded, and acknowledgement will be returned.
(*3) For ‘Not used’ items, if a single/multiple piece(s) of data Read/Write is/are executed, Error code 1 (31H, Shinko protocol) or Exception code 2
(02H, Modbus protocol) will be returned.
(*4) For 00E5H (Manual control MV), if the following is written, Error code 3 (33H, Shinko protocol) or Exception code 3 (03H, Modbus protocol)
will be returned.
• When OUT1 is in ON/OFF control, and if any items except OUT1 low limit and OUT1 high limit values are written.
• When Heating side (of Heating/Cooling control) is in ON/OFF control, and if any items – except Heating side OUT1 low limit, OUT1 high limit
value, Cooling side OUT2 low limit and OUT2 high limit value – are written.
• When Cooling side (of Heating/Cooling control) is in ON/OFF control, and if any items – except Heating side OUT1 low limit to OUT1 high limit
value, Cooling side OUT2 low limit and OUT2 high limit value – are written.
(*5) If 00E9H (Program control Advance function) is read, Error code 1 (31H, Shinko protocol) or Exception code 2 (02H, Modbus protocol) will be
returned.
If any value except 0001H (Advance Perform) is written, Error code 3 (33H, Shinko protocol) or Exception code 3 (03H, Modbus protocol) will
be returned.
(*6) If 00FEH (Data clear) is executed, all values will revert to factory default values.
If communicating using parameters which are unequal to the factory default, it will be impossible to communicate. Set the communication
parameters again.
(Refer to Section ‘3. Setting Communication Parameters’.)
If 00FEH (Data clear) is read, Error code 1 (31H, Shinko protocol) or Exception code 2 (02H, Modbus protocol) will be returned.
If any value except 1234H (Clear data) is written, error code 3 (33H, Shinko protocol) or Exception code 3 (03H, Modbus protocol) will be
returned.