![Shinko BCS2 Скачать руководство пользователя страница 21](http://html.mh-extra.com/html/shinko/bcs2/bcs2_communication-instruction-manual_1258175021.webp)
21
• Response message from the slave in normal status
3.5 idle
characters
Slave
address
(01H)
Function
code
(10H)
Data item
(1000H)
Data
(000FH)
Error check
CRC-16
(84CDH)
3.5 idle
characters
1
1
2
2
2
(5) Read (Slave address 1, Program pattern data) (Read multiple pieces of data)
• A request message from the master (When reading the program pattern data on p.21)
3.5 idle
characters
Slave
address
(01H)
Function
code
(03H)
Data item
(1000H)
Amount of data
(000FH)
Error check
CRC-16
(010EH)
3.5 idle
characters
1
1
2
2
2
• Response message from the slave in normal status
3.5 idle
characters
Slave
address
(01H)
Function
code
(03H)
Number of
response bytes
(1EH)
1
1
1
Data
(00C8003C000A00C800780000012C001E000A012C003C0000000000780000H)
30
Error check
CRC-16
(F340H)
3.5 idle
characters
2
Data in the response message becomes as follows.
Data Item
Data
Data (Converted to Hexadecimal)
1000H
Step 1 SV
200
00C8H
1001H
Step 1 time
60 minutes (1:00)
003CH
1002H
Step 1 wait value
10
000AH
1003H
Step 2 SV
200
00C8H
1004H
Step 2 time
120 minutes (2:00)
0078H
1005H
Step 2 wait value
0
0000H
1006H
Step 3 SV
300
012CH
1007H
Step 3 time
30 minutes (0:30)
001EH
1008H
Step 3 wait value
10
000AH
1009H
Step 4 SV
300
012CH
100AH Step 4 time
60 minutes (1:00)
003CH
100BH Step 4 wait value
0
0000H
100CH Step 5 SV
0
0000H
100DH Step 5 time
120 minutes (2:00)
0078H
100EH Step 5 wait value
0
0000H