7.2 JC Command Table
If
(Shinko protocol, JC command allocated),
(Modbus ASCII, JC command allocated) or
(Modbus RTU, JC command allocated) is selected in [Communication protocol], the following JC
command can be used.
7.2.1 A Single Piece of Data Read/Write Command
Shinko
Command
Type
Modbus
Function
Code
Data Item
Data
20H/50H
03H/06H
0001H
SV1
Set value, Decimal point ignored
20H/50H
03H/06H
0002H
Not used
(*1)
20H/50H
03H/06H
0003H
AT/Auto-reset Perform/Cancel
0000H: AT/ Auto-reset Cancel
0001H: AT/ Auto-reset Perform
20H/50H
03H/06H
0004H
OUT1 proportional band
Set value, Decimal point ignored
20H/50H
03H/06H
0005H
OUT2 proportional band
(*2)(*3)
Set value, Decimal point ignored
20H/50H
03H/06H
0006H
Integral time
Set value
20H/50H
03H/06H
0007H
Derivative time
Set value
20H/50H
03H/06H
0008H
OUT1 proportional cycle
Set value
20H/50H
03H/06H
0009H
OUT2 proportional cycle
Set value
20H/50H
03H/06H
000AH Not used
(*1)
20H/50H
03H/06H
000BH EV1 alarm value
(*4)
Set value, Decimal point ignored
20H/50H
03H/06H
000CH EV2 alarm value
(*4)
Set value, Decimal point ignored
20H/50H
03H/06H
000DH Not used
(*1)
20H/50H
03H/06H
000EH Not used
(*1)
20H/50H
03H/06H
000FH Heater burnout alarm value
Set value, Decimal point ignored
20H/50H
03H/06H
0010H
Loop break alarm time
Set value
20H/50H
03H/06H
0011H
Loop break alarm span
Set value, Decimal point ignored
20H/50H
03H/06H
0012H
Set value lock
(*2)(*5)
0000H: Unlock
0001H: Lock 1
0002H: Lock 2
0003H: Lock 3
20H/50H
03H/06H
0013H
SV high limit
(*6)
Set value, Decimal point ignored
20H/50H
03H/06H
0014H
SV low limit
(*6)
Set value, Decimal point ignored
20H/50H
03H/06H
0015H
Sensor correction
Set value, Decimal point ignored
20H/50H
03H/06H
0016H
Overlap/Dead band
Set value, Decimal point ignored
20H/50H
03H/06H
0017H
Not used
(*1)
20H/50H
03H/06H
0018H
Scaling high limit
Set value, Decimal point ignored
20H/50H
03H/06H
0019H
Scaling low limit
Set value, Decimal point ignored
20H/50H
03H/06H
001AH Decimal point place
0000H: No decimal point
0001H: 1 digit after decimal point
0002H: 2 digits after decimal point
0003H: 3 digits after decimal point
20H/50H
03H/06H
001BH PV filter time constant
Set value, Decimal point ignored
20H/50H
03H/06H
001CH OUT1 high limit
Set value
20H/50H
03H/06H
001DH OUT1 low limit
Set value
20H/50H
03H/06H
001EH OUT1 ON/OFF hysteresis
Set value, Decimal point ignored
20H/50H
03H/06H
001FH OUT2 cooling method
0000H: Air cooling
0001H: Oil cooling
0002H: Water cooling
20H/50H
03H/06H
0020H
OUT2 high limit
Set value
20H/50H
03H/06H
0021H
OUT2 low limit
Set value
20H/50H
03H/06H
0022H
OUT2 ON/OFF hysteresis
Set value, Decimal point ignored