5. DESCRIPTION OF FUNCTION
VM-5S
-21-
5-7 OK ALARM / SPEED RELAY MODE
Each OK alarm and SPEED RELAY contact can be set to either normally de-energized or
normally energized.
Alarm contact operation
Monitor power ON
Monitor power
OFF
Normal state
Alarm state
NO contact NORMALLY DE-ENERGIZED
OPEN
OPEN
CLOSE
NO contact NORMALLY ENERGIZED OPEN
CLOSE
OPEN
NC contact NORMALLY DE-ENERGIZED
CLOSE
CLOSE
OPEN
NC contact NORMALLY ENERGIZED
CLOSE
OPEN
CLOSE
For details refer to 7. PARAMETER SETTING on page 26.
5-8 ALARM RESET MODE
The automatic reset of all alarm output and alarm lamps can be set when the measured value or
input signal returning to normal. In addition to above, the self-holding function can be also set
for each alarm output that holds the alarm condition until reset by setting RES key (inside of the
front panel) or by shorting between RES and COM terminal.
• OK alarm / SPEED RELAY reset is not possible until the output condition has been
released.
For details refer to 7. PARAMETER SETTING on page 26.
5-9 MONITOR OUTPUT / PULSE OUTPUT
The input signal from the sensor or the internally shaped pulse signal is output from the BNC
connector on the monitor front panel and buffer output terminal on the rear panel (VM-5G Single
Unit Instrument Rack, VM-5Y Relay Module Unit).
For details refer to 7. PARAMETER SETTING on page 26.
5-10 RECORDER OUTPUT
An analog signal proportional to the rotor speed is output from the terminal block.
5-11 SELF-DIAGNOSTIC FUNCTION
Any failures in the input system, such as sensor broken or imperfect connections, are detected, then
an OK alarm is contact-output and (simultaneously), the OK lamp flashes.