background image

 

8(44) 

 

1.1  Coding Principle 

 

1.2  Feature 

Standard configuration 

l

  Modularized design makes it easier to combine module units 1 to 15. 

Cooling capacity can be enlarged by increasing the number of modules 
or choose appropriate modules to connect to existing system.     

l

  The water route of the modules can be linked by one module connecting 

to the inlet/outlet water tube. No need to install the inlet/outlet water tube 
for each module alone. The rubber soft pipe is used to connect the 
modules for convenient construction.       

l

  Adopts imported components like scroll compressor, expansion valve 

which ensure stable performance. The whole unit will not stop due to one 
module failure. 

l

  When the whole unit is running, the microcomputer will auto adjust the 

performance of each module or open / shut respective module unit 
according to system load. The module unit adopts double compressors 
and its power adjustable range is enlarged after combination to save up 
power whenever possible.   

l

  Wired control system enables the main unit and its controller to be 

separated from each other. 

l

  Protection grade

IP54 

Accessory option 

l

  Optional RS485 communication realizes the remote monitoring and 

network function. 

Содержание SICC-120A-R2

Страница 1: ...SICC A R2 CFC free Refrigerant Air cooled Central Water Chiller Date Nov 2017 Version Ver B English...

Страница 2: ......

Страница 3: ...16 2 1 Working Principle 16 2 1 1 Working Flow Instruction 16 3 Installation and Debugging 17 3 1 Installation Notice 17 3 2 Select Installation Site 18 3 3 Bearing Platform 19 3 4 Hanging and Transp...

Страница 4: ...5 4 3 5 Menu Instruction of E Unit Switch 35 4 3 6 Menu Instruction of F Maintenance 36 5 Trouble shooting 38 6 Maintenance and Repair 39 6 1 Daily Repair and Check Items 40 6 2 Monthly Periodical Che...

Страница 5: ...re 3 1 Installation Space 18 Picture 3 2 Platform Installation 19 Picture 3 3 Hanging and Transporting of the Unit 20 Picture 3 4 Same Direction Way 1 22 Picture 3 5 Same Direction Way 2 22 Picture 3...

Страница 6: ...6 44...

Страница 7: ...prevent damage of the machine or personal injuries SICC A R2 series is applicable for cooling moulds to reduce product s molding cycle They can also be used for equipment cooling in order to maintain...

Страница 8: ...nient construction l Adopts imported components like scroll compressor expansion valve which ensure stable performance The whole unit will not stop due to one module failure l When the whole unit is r...

Страница 9: ...ny modifications of the machine must be approved by SHINI in order to avoid personal injury and damage to machine We shall not be liable for any damage caused by unauthorized change of the machine Our...

Страница 10: ...10 44 1 3 Technical Specifications 1 3 1 SICC A R2 Series Outline Dimensions SICC 60A R2 SICC 90A R2...

Страница 11: ...11 44 SICC 120A R2 Picture 1 1 Outline Dimensions 1 3 2 Flange Picture 1 2 Flange Outline Dimensions...

Страница 12: ...aporator Cooling flow Flow m3 h 10 3 15 5 20 6 Pressure loss kPa 27 39 2 49 Pipe Coupler inch 5 5 5 Condenser Type Fin Style Air cooled Condenser Blower power kW 1 68 2 2 3 36 Air quantity m3 h 26 000...

Страница 13: ...ner is designed for adults Keep children away from it 9 Any deeds trying to change its specification are dangerous 10 Don t use evaporable solvents oil or toluene to avoid accidents 11 Ensure this mac...

Страница 14: ...careful This symbol should take more careful hereby Attention No need for regular inspection because all the electrical parts in the control unit are fixed tightly 1 4 3 Signs and Labels This is for i...

Страница 15: ...man made installations operation and maintenances upon machines without referring to the Manual prior to machine using 2 Any incidents beyond human reasonable controls which include man made vicious...

Страница 16: ...after a pressure downfall it comes into shell tube evaporator The low temp low pressure and saturated refrigerant absorbs the heat from cooling water to low down its temp The shell tube evaporator s r...

Страница 17: ...s wire 4 The end of the electricity wire should be safe and firm 5 There phase electricity and five wires are utilized Connect the power to live wire N to zero wire and G to ground wire 6 Electric po...

Страница 18: ...ct imposed by high temperature vapor or oil stain 3 Avoid being spattered by water vapor when choosing installation site near cooling water tower so to avoid any short ciruit or creepage 4 Proper vent...

Страница 19: ...peration and prevent the vibration and noise transmission from interfering the under floors the absorber should be laid between the unit base and base platform Please maintain horizontal when install...

Страница 20: ...d then combine them finally 2 If the large scale machine cannot be decomposed then dig hole in the wall or earth to transport it Path adjustment Adjust with the wall floor to facilitate transporting O...

Страница 21: ...ank should be placed higher by at least 1m than top of the whole set of water distribution pipelines to buffer the water volume s expansion or contraction and the isolated backup water pressure to wat...

Страница 22: ...e gauge 6 Thermometer 7 Flowmeter 8 Solenoid valve 9 Rubber soft pipe Picture 3 4 Same Direction Way 1 Names of Parts 1 Stop valve 2 One Way valve 3 Y type Filtration valve 4 Pump 5 Pressure gause 6 T...

Страница 23: ...3 7 Essentials for Electric Wiring 1 The electricity supply should use special branch circuit 2 Wiring work should be conducted according to relevant national electric standards and grounding 3 Refer...

Страница 24: ...t circuit and helps to separately control the start stop of every compressor every incoming cable needs to equip proper amount of non fuse breaker Showed in the following photo 8 Inorder to ensure per...

Страница 25: ...ntroller of slave machine requires the slave machine to connect with the 220V power cable which can t use the shielded cable The common two core cable is available to connect between the slave machine...

Страница 26: ...eeds to use Water Chillers of displayer control it must ensure the displayer address is set as 32 3 8 4 Communication Connection 1 Specificaiton of Communication Connection If the control cable needs...

Страница 27: ...erface Diagram Note The communication cable plug in and plug out must be carried out when the controller is powered off Otherwise the communication interface would be damaged easily Note The communica...

Страница 28: ...ue on the displayer Enter Enter the selected sub menu or confirm the set value 4 2 Interface Operation 4 2 1 Initial Interface Initial interface first appears after the controller is electrified for 4...

Страница 29: ...od of on 3 There is no severe alarm 4 The unit has been activated by keyboard 5 The main machine unit has been activated this function only works in the subordinate machine Note If any of the above co...

Страница 30: ...ubordinate machines will be forced to start And when the main machine is in off state all subordinate machines will be turned off 2 Startup and shutdown of subordinate machine provided that the unit h...

Страница 31: ...ay Thus on Monday the unit is on in the periods of 8 00 12 00 and 14 00 17 00 and is off in the rest of time On Tuesday the unit is on in 8 00 17 00 and off in the rest of time Besides the unit is alw...

Страница 32: ...eration 4 2 5 Password Input and Change Enter the interface of password input and the cursor blinks after is pressed At that time keys of and can be pressed to change the value When you are sure the d...

Страница 33: ...be pressed to page up and down in this submenu Interface Index Description of Displayer Default Unit Description of Function A01 Current set point 12 Display the target temp of control and select the...

Страница 34: ...of Function B01 Clock Alter the current time B02 Input the password of clock 0 Enter after inputting the correct password Factory default password 0000 B03 Turn on and turn off the unit at fixed time...

Страница 35: ...be shared by controller so one displayer can be shared by 16 controllers That is to say datum of 16 controllers can be viewed in one displayer When the controller has access to the Internet unit switc...

Страница 36: ...erface Fb System Information Fb01 Version Display the version of current program and hardware Fc Summer Winter Fc01 State Summer Press Enter to switch between summer and winter Fd Operation Time Fd01...

Страница 37: ...the model is chosen through the input signal of digital value 2 Keyboard switch choose either refrigeration or heating by the menu maintenance parameter which is presented in the interface FC01 in det...

Страница 38: ...Check and reset 4 Edit the value for heat flow 5 Check and reset Compressor stops immediately after it starts 1 Air inlet or outlet gets hindered 2 Condenser is dirty 3 Bad ventilation due to bad lan...

Страница 39: ...pply unless emergncyoccurs 2 When failure occurs and machine stops press the main power switch alarm light will go out Check the failure and do not start the machine before trouble shooting 3 Check th...

Страница 40: ...tems 1 Check if the screws loosen 2 Clean indoor air conditioner box or filter of cool air blower 3 Check if the joint of the pipelines leaks 4 Check the wire to see if there is any damage the connect...

Страница 41: ...es Check all wires of the machine Check whether pressure gauges are accurate Check whether compressor temperature is normal Check whether cooling water circulation is normal 6 4 4 Weekly Check Check i...

Страница 42: ...ly Check and clean filter and expansion valve Check the whole machine condition Clean condenser 6 4 8 Yearly Checking Check whether the contactor is normal 6 4 9 3 year Checking PC board replacement N...

Страница 43: ...43 44 Attachment Electrical Diagram...

Страница 44: ...44 44...