14(49)
Table 1-3: Specification List (SIC-A-R2 50HZ)
Model SIC-
Item/Parameters
7.5A-R2 12A-R2
18A-R2
24A-R2
28A-R2
38A-R2
48A-R2
58A-R2
75A-R2 100A-R2 114A-R2
Ver.
C
C
C
C
D
D
B
B
B
B
B
Refrigerant
Capacity
1)
kW
7.5
12
18
24
28
38
48
58
75
100
114
Refrigerant
Capacity
2)
kW
9.5
14
24
32
38
45
64
76
90
121
135
Compressor
Type
Scroll
Power
2.9
4.2
6.4
8.72
9.36
12.25
17.44
18.72
24.86
33.58
37.29
Refrigerant
Weight (kg)
3.5
5.0
5.5
5.5
9.0
12.5
7.5x2
8x2
7.8x2+6.8
8.7x3
Control Mode
Thermostatic expansion valve
Type
R410A
Evaporator
Type
Tube-in-shell style
Condenser
Type
Fin style
Blower (kW)
0.19
0.55
2
×
0.23
2
×
0.385
2
×
0.6
2
×
0.78
2
×
1.03
2
×
0.85
2
×
1.92 2
×
2.2+1.5
3
×
2.2
Water Tank Capacity (L)
30
65
80
186
230
316
Pump
2)
(50Hz/60Hz)
Power (kW)
0.75 / 0.75 / 1.1
1.1 / 1.1 / 1.1
1.1/1.5/2.2
-/1.8/2.4
-/3.0/4.0
-/4.0/5.5
Pump Flow (L/min)
21.5
34.4
51.6
68.8
80.3
108.9
137.6
166.3
215.0
286.7
32.8
Working Pressure (kg/cm
2
)
3.3/3.7
/4.5
3.2/3.5
/4.4
2.8/4.1
/4.9
2.7/3.85
/4.5
3.1/3.9
/4.9
2.4/3.8
/4.6
-/3.4/4.5
-/3.2/4.3 -/3.5/4.1 -/3.1/3.9
-/3.7/4.9
Total Power (kW) (50Hz/60Hz)
3.8/3.8
/4.2
5.5/5.5
/5.9
7.8/7.8
/7.8
10.6/10.6
/10.6
11.7/12
/12.8
14.9/15.3
/16
-/21.3
/21.9
-/22.2
/22.8
-/31.7
/32.7
-/42.5
/43.5
-/47.9
/49.4
Pipe
Coupling (inch)
Cooling Water Outlet
1
1
1
/
2
2
2
1
/
2
Water Tank Inlet
1
1
1
/
2
2
2
1
/
2
Water Tank Drainage Port
1/2
1
Water Tank Overflow Port
1/2
1
Protective
Devices
Compressor
Overload relay
Pump
Overload relay
Cooling Water Circuit
High and low pressure switch/anti-freeze switch
Water Circuit
Flow switch/Water level switch (Optional)/By-pass valve
Operation Noise dB (A)
78
75
74
78
81
86
84
82
86
90
90
Power(VAC)
3
Φ
, 400VAC, 50Hz
Measures Exchange
1 kW = 860 kcal/hr 1 RT = 3,024 kcal/hr 10,000 Btu/hr = 2,520 kcal/hr
Note: 1) Refrigeration capacity 1 is based on the flow 0.172 m3 / (h.k W) the chilled water outlet Temperature of 7
℃
/44.6
°
F and the environment temperature of 35
℃
/95
°
F.
2) Refrigeration capacity 2 is based on the flow 0.172 m3 / (h.k W) the chilled water outlet Temperature of 20
℃
/68
°
F and the environment temperature of 30
℃
/86
°
F.
3) It is the working pressure of water pump when negative pressure of inlet water is 0.
4) Low pressure pump is for domestic and Southeast Asia export, customers can change for medium pressure pumps (use P for short; e.g.: SIC-and A-R2-P) or high
pressure pumps (use HP for short; e.g.: SIC-and A-R2-HP), specific parameters in turn as shown above.
5) Pump power is included in total power.
6) Special orders of machine voltage can be acceptable according to customers
’
s request.
7) The air-cooled water chiller is applicable to the conditions under the environment temperature of 43
℃
/109.5
°
F.
Содержание SIC-A-R2
Страница 1: ...SIC R2 Operation Manual of CFC free Refrigerant Water Chiller Date Jun 2017 Version Ver D English...
Страница 2: ......
Страница 6: ...6 49...
Страница 40: ...40 49 6 Maintenance and Repair A Water cooled Series...
Страница 41: ...41 49...
Страница 42: ...42 49 B Air cooled Series...