6) After the installation is completed, check if there are leakages in the
circulation system. Cooling water circulation pipe should be covered with a
layer of insulated material to avoid temperature increasing and water drops
forming on the surface of circulation pipe.
7) This seires of models mainly use cooling tower
’
s circulation to cool down the
water. During the installation, users should provide enough cooling water to
the water chiller. Otherwise, machine would over high pressure and reduce
cooling capacity. The dimension of cooling water inlet/outlet and the flow
please refer to 1.3 Technical Specifications. Cooling water pressure should
be 2.5~4bar, cooling water temperature is suggested at 25~35 .
℃
8) Water used in the system must be processed since water with high PH may
cause corrosion to copper tube and lower the lifetime of the machine. Use
water with pH ranged 7.0~8.5.
3.4
Water Tank Filling
The filling port of this series model has connected to the water-tank circulation
loop of the condenser. As long as the circulation loop works normally, it can
ensure the normal filling of the water tank. Air-cooled series are reserved with
water tank filling port. Please refer to label explanation in 1.4.2 for connecting
water supply.
Attention!
Don
’
t start up the water chiller before the tank is full filled with water!