27(49)
3. Installation and Debugging
Attention!
Read this chapter before installation. Install the machine according to
following steps!
3.1 Machine Location
1) Water chiller should be installed in an environment that has good
ventilation, such as draughty area near the window. Ambient temperature
should not be more than 43
℃
. Use ventilator or exhaust pipe to conduct the
hot air produced by the chiller to the outside. If the chiller is installed outdoors,
protective cover should be used.
2) Please ensure at least 1m installation and maintenance space around the
machine.
3.2 Power Connectors
1) Make sure that the voltage and frequency corresponds with the requirements
on manufacturer's name plate.
2) Connection of the machine electrical wires and negative wire according to
local rules and regulations.
3) Use independent electrical wires and switch. Diameter of electrical wire
should not be smaller than that of the electric wire which is used for the
electrical control box.
4) Wiring connections should be firmly fixed.
5) The chiller use three phase & five core wire. Connect wire N to null wire, G to
earth wire, and others to live wire.
6) Power supply:
Voltage deviation: Rated voltage on the nameplate:
±
5%
Frequency deviation:
±
2%
7) Specific power supply specifications please refer to the schematic model.
Electrical wire connection of water chiller should be done by qualified
electrician! Electrical wiring circuit should not be modified unless