34(43)
4.5.2 Default parameter setting
Table 4-5
:
Default Parameter Setting
No.
Code
Meaning of parameter
Default value
Remark
1
st
Set point of out 1
7
Unit:
℃
2
rd
Temp. difference relative to out 1
2
Unit:
℃
3
r1
Minimum value of st
7
Unit:
℃
4
r2
Maximum value of st
35
Unit:
℃
5
st2
Set point of out 2
2
Unit:
℃
6
rd2
Temp. difference relative to out 2
2
Unit:
℃
7
c2
Min. shutdown time of out 1
2
Unit min
8
c3
Min. boot time of out 1
2
Unit min
9
c22
Min. shutdown time of out 2
3
Unit min
10
c23
Min. boot time of out 2
2
Unit min
11
c0
Min. start interval of out1 and out2
60
Unit S
12
c1
Start delay of out1 after powering
on
2
Unit min
13
AH
High- temp. alarm threshold value
/ deviation (AH=0; alarm disabled)
35
Unit:
℃
AL
Low- temp. alarm threshold value /
deviation (AL =0; alarm disabled)
5
Unit:
℃
14
Ad
Temp. alarm shutdown delay
0
Unit min
Note: 1.This parameter is only applicable to temperature controller PZXNS0G001 version. Do not use this
parameter for other models or versions.
4.5.3 Parameter setting method
When setting, press and hold the
key for more than 3 secs, an adjustable
“
PS
”
will appear on the screen. Press
button and then the
button to
enter the password 22. When setting parameters, it must press the
key till
it returns to the temp. display interface. Otherwise, the set parameters will not be
saved.
Attention!
The parameter of the temperature controller has been set before delivery.
Don
’
t set the parameters unless otherwise specified.