29(43)
increase or decrease the temperature setting value. The minimum
temperature of this series of water chillers is set to 7
℃
(no lower than
5
℃
).
5) Anti-freezing setting: anti-freezing switch is equipped (setting value 5
).
℃
When process water temperature is lower than 5
, the compressor
℃
will
stop working.
Attention!
Pump rotating direction must be correct.
Attention!
Before startup, make sure to turn on the cooling water pump. Check the
water tank of the water chiller, and don
’
t start the machine when there
’
s no
water left in the water tank. Otherwise, the company will not be responsible
for the machine damage.
Attention!
In order to reduce the possibilities of machine damage and prolong the life,
start the machine with correct methods.
Attention!
The temperature of the electronic thermometer should not be lower than
5
.
℃
The temperature of anti-freezing switch and high and low pressure
switch is already set before delivery. We shall not be liable for any damage
caused by unauthorized change of the setting.