11(43)
Model
Item/
Parameters
SIC-20A
SIC-25A
SIC-30A
SIC-40A
SIC-45A
SIC-50A
Refrigerant
Capacity
1)1
kW
52
60
76
104
114
120
Kcal/hr
44,720
51,600
65,360
87,720
98,040
103,200
Compressor
output
power
(Hz)
kW
16.12
19.94
23.6
26.28
35.4
36.44
HP
20
25
30
40
45
50
Refrigerant
Weight (kg)
18
22
26
34
42
48
Control Mode
Thermostatic expansion valve
Type
R22
Evaporator
Type
Tube-in-shell style
Condenser
Type
Tube-fin style
Blower power (kW)
0.8
×
2
1.1
×
2
1.5
×
2
1.1
×
3
1.5
×
3
1.5
×
4
Water Tank Capacity (L)
180
200
270
400
650
Water pump
2)
(50Hz)
Power (kW)
2.2/3/4
4/3/4
4/4/5.5
Pump flow (L/Min)
200/300/300
300/300/300
533/366/367
Pump pressure
(kgf/cm
2
)
2.5/3/4.2
2.7/3.4/4.3
Total Power (kW)
3)
19.92
22.62
31.3
39.66
44.95
46.44
Pipe
Coupling
(inch)
Cooling Water
Outlet
2
2
1
/
2
2
1
/
2
Cooling Water Inlet
2
2
1
/
2
2
1
/
2
Water Tank Outlet
1
Water Tank Port
1/2
1
Protective
Devices
Compressor
Overload relay
pump
Overload relay
Cooling Water
Circuit
High and low pressure switch/anti-freeze switch
Water Circuit
Flow switch (optional) / water tank level sensor (optional) / bypass valve
Power(VAC)
4
)
3
Φ
,400V,AC 50HZ
Measures Exchange
Kw=860 kcal/hr 1RT=3,024kcal/hr 10,000Btu/hr=2,520kcal/hr
We reserve the right to change
specifications without prior noice.
Note:
1) Refrigeration capacity is measured based on the flow 0.172 m
3
/ (h.k W) and the outlet temperature (7
℃
) of
chilled water under the environment temperature of 30
℃
.
2) Low pressure pump is for domestic and Southeast Asia export, customers can change for medium
pressure pumps (use P for short; e.g.: SIC-5A-P) or high pressure pumps (use HP for short; e.g.:
SIC-5A-HP), specific parameters in turn as shown above.
3) Pump power is included in total power.
4) Special orders of machine voltage can be acceptable according to customers
’
requests.
Содержание SIC-10A
Страница 1: ...SIC A Air cooled Water Chillers Date May 2021 Version Ver B English...
Страница 2: ......
Страница 37: ...37 43 6 Repair and Maintenance...