The equipment includes monitor lamps for
"WATER TEMP" , "CHARGE" , "OIL PRESS"
and "SPILL CONTAINMENT" .
If the equipment is normal, the "CHARGE" and
"OIL PRESS" monitor lamps light up when the
starter switch is switched from "STOP" to
"RUN" , and all monitor lamps turn off when the
engine is started. If any error besides that of
spill containment occurs during operation, the
corresponding monitor lamp lights up and the engine is automatically stopped.
If the engine is automatically stopped, return the starter switch to "STOP" and
restart the engine. Watch the lit/unlit status of the monitor lamps the next time an
automatic stop occurs and check the error contents.
(1) Water Temperature Monitor Lamp
The water temperature monitor lamp ("WATER TEMP") lights up and the engine
is automatically stopped if the cooling water temperature becomes irregularly
high during operation. If this occurs, inspect the water level of the sub tank and
add cooling water if the water level is insufficient. (Refer to section "6-2. Cooling
Water Inspection".)
If the cooling water in the sub tank is at the specified level, it is probable that
overloading is the cause. Use within the rated output.
(2) Battery Charge Monitor Lamp
The battery charge monitor lamp ("CHARGE") lights up and the engine is
automatically stopped if battery charge fails during operation. If this occurs, it is
probable that there is fan belt damage or a wiring fault. Request repair at the
retail outlet where the equipment was purchased.
<Note>
•
The charge monitor cannot detect battery deterioration or insufficient battery fluid.
Inspect the battery fluid level periodically. (Refer to section "6-6. Battery
Inspection".)
(3) Oil Pressure Monitor Lamp
The oil pressure monitor lamp ("OIL PRESS") lights up and the engine is
automatically stopped if the engine oil pressure drops during operation. If this
occurs, inspect the engine oil level and fill with engine oil until it reaches the
maximum level.
<Note>
•
The oil pressure monitor cannot detect oil deterioration.
•
Change the engine oil periodically. (Refer to section "11.Inspection/Maintenance".)
•
The charge monitor cannot detect battery deterioration or insufficient battery fluid.
Inspect the battery fluid level periodically. (Refer to section "6-6. Battery
Inspection".)
•
Inspect the fuses if the engine is automatically stopped and none of the monitor
lamps ("WATER TEMP", "CHARGE" and "OIL PRESS") light up. (Refer to section
"4. Part Names" for fuse location.)
If a fuse has blown, it is probable that there is a fault in an electric part or the wiring.
Request repair at the retail outlet where the equipment was purchased.
Water Temp
Charge
Oil Press
Spill
Containment
Содержание DGW340DM
Страница 2: ......
Страница 46: ...43 14 Engine Wiring Diagram...
Страница 47: ...44 P 1 3 15 Generator Wiring Diagram...
Страница 48: ...45 P 2 3...
Страница 49: ...46 P 3 3...
Страница 50: ...47 MEMO...
Страница 51: ...48 MEMO...
Страница 52: ...49 2021...