Problem
Suspected cause
Action
Engine starts but
stalls immediately
1. Fuel filter is clogged.
2. Water is interfused in fuel line.
3. Air is interfused in fuel line.
4. Poor piping connection to external fuel tank.
5. Air filter element is clogged.
6. Lubricant oil is insufficient.
7. Emergency operation/Fault detection.
1. Clean/Change fuel filter.
2. Drain water in water
separator, fuel filter or fuel
tank.
3. Extract the air.
4. Check piping connection.
5. Check/Change air filter
element.
6. Supply lubricant oil.
7. Ask our distributor to repair.
Engine oil pressure is
low
1. Lubricant oil is insufficient.
2. Oil filter is clogged.
3. Oil Pressure switch is defective.
4. Wrong oil is used.
1. Supply lubricant oil.
2. Change oil filter.
3. Ask our distributor to repair.
4. Change to proper kind and
viscosity oil.
Overheated
1. Engine thermostat is defective.
2. Water temp sensor is defective.
3. Controller is defective.
4. Fan belt tension is weak.
5. Coolant is insufficient.
6. Radiator core is clogged.
1. Ask our distributor to repair.
2. Ask our distributor to repair.
3. Ask our distributor to repair.
4. Check/Adjust fan belt.
5. Check/Supply coolant.
6. Clean radiator core.
Black smoke comes
out from muffler
1. Air filter element is clogged.
2. Fuel injection nozzle is defective.
3. Improper fuel is used.
1. Check/Change air filter
element.
2. Ask our distributor to repair.
3.Change to clean fuel.
White smoke comes
out from muffler
1. Too much or too little oil to cylinder.
2. Water is interfused in fuel line.
3. Fuel injection nozzle is defective.
4. Coolant temperature is too low.
5. Engine thermostat is defective.
1. Ask our distributor to repair.
2. Drain water in water
separator, fuel filter or fuel
tank.
3. Ask our distributor to repair.
4. Warm-up driving is needed.
5. Ask our distributor to repair.
Voltage value does
not change
1. Controller is defective.
2. AVR is defective.
3. Disconnected circuit, loose terminal or
departed.
4. Initial exciter is defective.
5. Alternator is defective.
6. AVR protective device operation.
1. Ask our distributor to repair.
2. Ask our distributor to repair.
3. Ask our distributor to repair.
4. Ask our distributor to repair.
5. Ask our distributor to repair.
6. Replace AVR fuse.
The voltage does not
rise to the rated
voltage
1. Controller is defective.
2. AVR is defective.
3. Voltage regulator dial is defective.
4. Frequency is low.
1. Ask our distributor to repair.
2. Ask our distributor to repair.
3. Ask our distributor to repair.
4. Ask our distributor to repair.
The voltage value
exceeded the rated
voltage
1. Controller is defective.
2. AVR is defective.
3. Improper load cable connection.
1. Ask our distributor to repair.
2. Ask our distributor to repair.
3. Correctly set the connection
location to the output
terminal.
The voltage drops
drastically when
connecting to load
1. AVR is defective.
2. Unbalanced loads sharing to each terminal.
3. The current of the used equipment exceeds
the rated current.
Loads total exceeds the rated current.
4. Over load.
5. AVR protective device operation.
6. Frequency selector is wrong setting.
1. Ask our distributor to repair.
2. Balance the loads sharing to
each terminal.
3. Change to a device with an
available capacity.
4. Decrease the loads to meet
the rated output.
5. Replace AVR fuse.
6. Set to properfrequency.