Protection Feature List
No.
Action
Abnormality
Earth
Leakage
Relay
Active
Breaker
Trip
Engine
Automatic
Shutdown
Warning
Indicator
Flash
Controller
display
Cause
1
Low Oil
Pressure
Activate due to low oil pressure in the engine
Default : 0.49
100 kPa
2
High Coolant
Temperature
Activates due to high water temperature in the
engine. Default : 115°C
3
Air Filter
Clogging
The element is clogged making it necessary to
clean or replace the element.
4
Overload
Activates in overload
Flashes when at approx. 80% of rated output.
Load rejection when the rated output is
exceeded.
5
Fail to Start
The engine fails to start three times
6
Water In Fuel
When the water separator is full of water.
7
Charge Alt
Failure
Activates in battery charge Impossible
8
Fuel Level Low
The amount of fuel is small
9 Current Leakage
Activates in current leakage
*
indicates the automatic activation.