16
Selection of Rated Sensitivity Current
Current
setting
Slide switch position
Switch
1
2
3
4
30mA
(Operating
time:0.04
sec. or less)
ON
OFF
※
1
100mA
ON
OFF
300mA
ON
OFF
500mA
ON
OFF
1000mA
ON
OFF
Selection of Operating Time
(not applicable to 30mA)
Time
setting
Slide switch position
Switch 5
6
7
8
0.04sec.
or less
ON
OFF
0.3sec.
(0.2-0.36
sec.)
ON
OFF
0.5sec.
(0.4-0.6
sec.)
ON
OFF
1sec.
(0.8-1.2
sec.)
ON
OFF
2sec.
(1.3-2sec.)
ON
OFF
<Note>
※
1: Whenever Switch1 is set to
「
ON
」
position, the setting is back to default
as 30mA/0.04sec, regardless of Switch2
~
8 position.