- 36 -
:Fire
Always wipe any drip of gasoline or oil.
①
①
①
①
Add fuel to the fuel tank
②
②
②
②
Turn the starter switch to <RUN> position. It will take approximately 30 seconds to
vacuum the air out.
<Caution>
Ensure that all the air is completely extracted from fuel line, by setting the throttle lever
to IDLING and start the engine. In the case air is in the fuel line, the engine speeds is
unstable, and proceed with the vacuuming steps again.
9.4 Stopping the Generator
①
①
①
①
Turn the switch and the circuit breaker for the load equipment to OFF
②
②
②
②
Turn the circuit breaker for single-phase and 3-phase on the control panel to OFF
position
③
③
③
③
Set the throttle lever to IDLING
④
④
④
④
Keep the engine idle (cooling down) for at least 3 minutes
⑤
⑤
⑤
⑤
Turn the starter switch to STOP position
9.5 Protection Features
This generator is equipped with automatic shutdown feature and display of the location of alarm,
in event of any alarm situation. In event of the automatic shutdown or alarm lamp flashing, turn
off the engine and investigate the alarm.
Protection Feature List
Action
No.
Symptoms
Circuit
Breaker
OFF
Automatic
Engine
Shutoff
Alarm
Lamp
Flash
Cause
1
High Coolant
temperature
--
○
○
○
○
○
○
○
○
Engine coolant temperature
is too high
(default at 105 degrees Celsius)
2
Oil pressure
drop
--
○
○
○
○
○
○
○
○
Engine oil pressure dropped
(default at 0.98 x 100kPa)
(1.0kg/cm
2
)
3
Insufficient
battery
charge
--
--
○
○
○
○
When the battery can no longer
hold charge
4
Current
leaks to the
earth
○
○
○
○
--
○
○
○
○
When current leaks to the earth
5
Overload
○
○
○
○
--
--
When the circuit overloads
○
○
○
○
indicate the automatic feature
Caution