6
.
Serial Communications Settings
9
6.2. Cable Wiring
For details on cable wiring, refer to
SECTION 3 Installation and Wiring
of the
CJ Series Serial
Communications Units OPERATION MANUAL
(Cat. No. W336).
Check the shapes and pin layouts of the connectors before wiring.
Shape and pin layout of the connector
Serial Communications Unit (CJ1W-SCU42) applicable connector: D-SUB 9-pin female
Pin No.
Abbreviation
Signal name
I/O
1
FG
Shield
―
2
SD
Send data
Output
3
RD
Receive data
Input
4
RS
Request to send
Output
5
CS
Clear to send
Input
6
5V
Power supply
―
7
DR
Data set ready
Input
8
ER
Data terminal ready
Output
9
SG
Signal ground
―
Shell
FG
Shield
―
ATX-R/ATY-R series applicable connector: D-SUB 9-pin male
Use
Pin No.
Abbreviation
Signal name
RS-232C
1
―
―
2
RXD
Data input
3
TXD
Data output
4
DTR
Handshake (send)
5
SG
Signal ground
6
DSR
Handshake (receive)
7
RTS
Request to send (RS-232C)
8
CTS
Clear to send (RS-232C)
9
―
―
Cable and pin layout
Serial Communications Unit
(CJ1W-SCU42)
ATX-R/ATY-R series
RS-232C
Interface
Signal
name
Pin No.
Pin No.
Signal
name
RS-232C
Interface
FG
1
1
NC
SD
2
2
RXD
RD
3
3
TXD
RS
4
4
DTR
CS
5
5
SG
5V
6
6
DSR
DR
7
7
RTS
ER
8
8
CTS
SG
9
9
NC
FG
Shell
D-SUB 9-pin
cable connector: female
D-SUB 9-pin
Cable connector: male