- 12 -

: Address (Machine No.)

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • 

Two digits 

Two-digit address data (00~99) set in the controller is
divided to the higher position (tens) and the lower
position (units) and each is shown by an ASCII code. 

: Text

•••••••••••••••••••••••••••••••••••

A group of a command and data,
in the format of each command.

: End character.

• • • • • • • • • 

(3AH)  Shows the end of the
block. 

: BCC check

• • • • • • • • • • • • 

BCC check data is shown in two
digits. 

A value obtained by exclusive OR operation of data
following @(data in the higher position of the address)
through : is converted to two ASCII characters and
shown by two digits in the higher and lower positions.

(Example)  BCC operation of DI read command (Address: 01)

: Terminator

• • • • • • • • • • • • 

CR(0DH)  Shows the termination

of the data of the block.

(2) In this protocol, address data is inserted in the block in each

transmission or response and so no data link needs to be
established or aborted. 

(3) The apparatus which has the address matches the one in the

command block, interprets the command, data, etc., and
returns a response block by inserting the same address into it. 
Apparatuses which the addresses do not match the one in the
block wait for the next block without activating. 

(4) In the case of receiving block data and the terminator CR is

not completed in about 1 second after receiving the start
character, it designates a time-out and automatically waits for
the next command, that is, the start character @ is being
waited for.

7-5. Text 

7-5-1. Text format

The text format is classified into read data, write data and
response data.

(1) Read Data 

@

0

1

D

1

:

BCC

CR

(40H)

(30H)

(31H)

(44H)

(31H)

(3AH)

(34H)(45H)

(0DH)

30H +

31H +

+

44H + 31H + 3AH=4EH

BCC=(34H), (45H)

4

E

In the above,        =EX-OR (exclusive OR)

••

(2) Write Data

(3) Response Data 

Response data has different formats depending on whether
read data has been received or write data has been received. 

Response data to read data received

Appropriate read data contents of commands shown in
the table of the read data text format are sent back. 
Response data to write data received 

The same data as the received write data is sent back.

7-5-2. Data format

The data format is divided to 3 categories; numerical data, 1 byte
data and special data. 

(1) Numerical Data (-2999~9999) 

The length of numerical data in the text is fixed to six
characters including a code and a decimal point.  A code (+
or -) is attached to the head of the numerical data.  In the case
where the numerical value including a code is less than six
characters, 0 is inserted between the code and the figure or
figures to make the value six characters.  When a code is
excluded, each of the 5 characters is a figure or a decimal
point. 

Examples of numerical data

*1
 

Command

The text format of read data contains only of a 
command of two characters. 

Command

Contents of Read Data

PV value, Execution SV value*1, Control output value, 
Stop (STBY) status, Manual (MAN) status, AH status, 
AL/HB status, AT status, SB status.

Set value of higher limit alarm (AH), Set value of lower 
limit alarm (AL).
Load current value, Set value of heater break alarm (HB).

Set value of set value bias (SB).

Set value of hysteresis (DF).
Set value of manual reset (MR).
Set value of PV bias, Set value of PV filter.
Set value of proportional cycle time.

Set value of soft start time.
Communication mode, Delay time.

Proportional band (P) value, Integral time (I), Derivative 
time (D) value, Set value of target value function (SF).

Set value of lower limit output limiter, Set value of 
higher limit output limiter. 

D1

D2

D3
D4

D5

D6
D7
D8
D9

DA

DB
DC

The execution SV value is a total of the SV value and the 
value bias.

Command

Command

Write data

The text format of write data 
contains a command and write data 
value. 

Contents of
Write Data

Attribute Command

Contents of
Write Data

Attribute

SV value

E1

E2

E3

E4

E5

E6

E7

E8

E9

EA

EB

EC

ED

EE

EF

Numerical
value

Numerical
value

1 byte

*2

Control output value

Stop status

1 byte

Manual status

1 byte

AT status

Numerical
value

Higher limit alarm 
(AH) value

F1

Numerical
value

PV bias value

F2

Numerical
value

PV filter value

F3

Numerical
value

Proportional cycle 
time

F4

Numerical
value

Lower limit output 
limiter value

F5

Numerical
value

Higher limit output 
limiter value

F6

Numerical
value

Soft start time value

F7

1 byte

Communication 
mode

Numerical
value

Lower limit alarm 
(AL) value

Numerical
value

Heater break alarm 
(HB) value

Numerical
value

Set value bias (SB) 
value

Numerical
value

Proportional band 
(P) value

Numerical
value

Integral time (I) value

Numerical
value

Derivative time (D) 
value

Numerical
value

Target value function 
(SF) value

Numerical
value

Hysteresis (DF) value

Numerical
value

Manual reset (MR) 
value

*2   SV value is target set value. 

Command

Data 1

Data 2

,

Data n

,

,

Command

Write data

Numerical data (30H~39H) or a decimal point (2EH)
Code + (2BH) or – (2DH)

Numerical value

+

-

1

0.01

1234

12.34

0 or OFF

+

+

+

+

+

0

0

0

0

1

1

2

3

4

5

6

0

0

.

0

1

0

1

2

3

4

1

2

.

3

4

0

0

0

0

0

-1

-0.01

-123.4

-12.34

-0.001

0

0

0

0

1

1

2

3

4

5

6

0

0

.

0

1

1

2

3

.

4

1

2

.

3

4

0

.

0

0

1

Содержание SR73A Series

Страница 1: ...o the instrument On the terminal nameplate affixed to the case of your instrument the mark is printed This is to warn you of the risk of electrical shock which may result if the charger is touched while it is energized A means to allow the power to be turned off such as a switch or a breaker should be installed in the external power circuit to be connected to the power terminal of the instrument F...

Страница 2: ... 14 8 Specifications 15 4 1 Introduction 1 1 Check before use This product has been fully checked for quality assurance prior to shipment Nevertheless you are requested to make sure that there is no error damage or shortage of delivered items by confirming the model codes and checking the external view of the product and the number of accessories Confirmation of Model Codes Check the model codes s...

Страница 3: ...th 48 height 91 6 width 44 6 Dimension of current transformer CT for heater break alarm For 0 30A CTL 6 S For 0 50A CTL 12 S36 8 unit mm 2 5 Wiring 1 Wiring operation should be done according to the instruction for the terminal arrangement in section 2 6 Exercise care that no wrong connection is made 2 Crimp terminal should accommodate the M3 5 screw and should have a width of less than 7mm 3 For ...

Страница 4: ...nitor LED green On selection by ON turns on AT waiting key flashes on AT execution 3 AH alarm output monitor LED red Turns on for higher limit alarm output ON 4 AL HB alarm output monitor LED red Turns on for lower alarm output ON or heater break alarm ON 5 MAN manual control output monitor LED green Flashes when control output is in manual operation 6 STBY control output stop monitor LED green Tu...

Страница 5: ... decimal point in the rightmost position on the top row flashes Press the or key to change the lower limit value and press the key to register the data Upon registering the lower limit value data the decimal point in the rightmost digit in the bottom row begins to flash Change the higher limit value by pressing the or key and register it by means of the key Upon registering the higher limit value ...

Страница 6: ...ualoperation 0 100 Themeasuredvalue PV isdisplayedonthetopandthecontroloutput valueonthebottom PressingtheMANkeyonthisscreenswitches autotomanualandviceversa RefertoItem4 6 1 fordetail Control execution stop selecting screen Initialvalue EXEC Settingrange EXEC STBY Execution orstop ofcontrolisselected RefertoItem4 6 2 fordetail AT auto tuning action control screen Initialvalue OFF Settingrange OFF...

Страница 7: ...ockissetonlockNo 1 2or3 noselectioncanbeperformedevenifthedigitpointis flashing Digits and arenotshownincaseofnooption Digitsof and arenotdisplayed Measuring range code select digit Initialvalue Multi05 Voltage V 81 Current95fixed Selectingtwodigitsfrom 4 5 Measuringrangecodetable Control output characteristic select digit Initialvalue RA heatingcharacteristics DA coolingcharacteristics RefertoIte...

Страница 8: ...the higher limit value is forced to be the lower limit value 1 Therefore the higher limit value cannot be set to be less than the lower limit value 1 ENT Note Moving to another screen while maintaining the manual mode is possible In this case it should be noted that control output is made manually The apparatus is in the manual mode when the MAN monitor LED is flashing ENT 6 1 14 Soft Start Time S...

Страница 9: ...m option is added and the lower limit alarm of the alarm type select digit on the function selecting screen of the mode 2 group screen group is selected Lower limit deviation value alarm is output for measured value to be less than set value alarm set value For lower limit deviation value alarm if set value alarm set value is less than the lower limit of the measuring range the action point is low...

Страница 10: ...nd 74A series two types of communication interface RS 422A and RS 485 are available Each enables a personal computer or the like to set and read various data by the use of signals which conform with EIA standards RS 422A and RS 485 are communication standards established by the Electric Industries Association EIA which are meant for electrical or mechanical matters the so called hardware but not f...

Страница 11: ...ront panel turns on and the commands for read and write through communication become valid Front key operation works only to change from remote to local 7 3 2 Communication address setting screen RS 422A and RS 485 allow connection of a plurality of apparatuses but in fact communication is carried out between two apparatuses Therefore the address of each apparatus is designated by a number between...

Страница 12: ... value including a code is less than six characters 0 is inserted between the code and the figure or figures to make the value six characters When a code is excluded each of the 5 characters is a figure or a decimal point Examples of numerical data 1 Command The text format of read data contains only of a command of two characters Command Contents of Read Data PV value Execution SV value 1 Control...

Страница 13: ...No did not match The end character was not CR 0DH A hardware error such as a framing error overrun or a parity error occurred 7 5 5 Restrictions by commands etc 1 Restrictions by Read Command Upon receiving the D1 read command the status of unequipped options AH AL HB SB become 0 30H 2 Restrictions by Write Command In the case of P OFF and Y and P output write data of E2 write command of manual ou...

Страница 14: ...xt Data 3AH BCC CR 0DH Higher position Lower position Higher position Lower position Received data Transmitted data D1 D1 STBY MAN AH AL AT SB 0 30H or 1 31H PV value SV value Output value Received data Transmitted data D2 D2 Set value of AH Set value of AL Received data Transmitted data D3 D3 CT current value Set value of HB Received data Transmitted data D4 D4 Set value of SB Received data Trans...

Страница 15: ... Sampling cycle 0 5 sec PV bias range 200 unit PV filter 0 100 sec 0 without filter Control Control mode Auto tuning PID ON OFF control Proportional band P Off 0 1 999 9 FS Off setting On Off action Integral time I Off 1 6000 sec Off setting P PD action Derivative time D Off 1 3600 sec Off setting P PI action Manual reset MR 50 0 50 0 Valid when P OFF and I OFF Output limiter Lower limit limiter 0...

Страница 16: ...tact type or the SSR drive voltage type Alarm action Heater amperage detected by externally attached CT except 0 5V DC input Alarm output On upon detection of heater break while control output is On Current setting range Off 0 1 50 0A Alarm action stops when Off is set or Off 1 500A when 0 5 V DC for CT input is selected Setting resolution 0 1A or 1A Amperage display 0 0 55 0A or 0 550A Display ac...